Inspections for the day of: Tuesday, May 3, 2005.
Number of inspections: 24
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00154 INSP-Final Inspection5/2/20055/3/20055/3/2005 5:40:05 PMPCANC
harry; Phone #: ###-#### Ran out of time to do inspection.
BLD02-03021 FIRE-Final Inspection5/2/20055/3/20055/3/2005 5:39:24 PMAFAIL
carl; Phone #: ###-#### Provide sheet Rev12 for smoke detector placement. Meet requirements for detector type and placement per 1999 edition of the nfpa 72. Paint text on curbing per review comments.
BLD02-03020 FIRE-Final Inspection5/2/20055/3/20055/3/2005 5:38:58 PMAFAIL
carl; Phone #: ###-#### Provide sheet Rev12 for smoke detector placement. Meet requirements for detector type and placement per 1999 edition of the nfpa 72. Paint text on curbing per review comments.
BLD02-03019 FIRE-Final Inspection5/2/20055/3/20055/3/2005 5:38:40 PMAFAIL
carl; Phone #: ###-#### Provide sheet Rev12 for smoke detector placement. Meet requirements for detector type and placement per 1999 edition of the nfpa 72. Paint text on curbing per review comments.
BLD05-00342 FIRE-Final Inspection5/2/20055/3/20055/3/2005 3:40:39 PMPFAIL
###-#### - lannie Repair or replace the emergency light in the dining area. Remove or disable the thumbturn deadbolts on doors and provide approved hardware on the womens restroom door and the door to the storage room from the kitchen.
FIR04-00684 INSP-Sprinkler Rough-in/Hydro5/2/20055/3/20055/3/2005 3:12:51 PMAPART
Looked at the fourth floor corridor piping. Notified Tom that resubmitals will be required.
BLD05-00394 FIRE-Final Inspection5/2/20055/3/20055/3/2005 2:29:19 PMAFAIL
Provide emergency lighting in the short exit corridor on the south end per approved drawings.
BLD03-02531 FIRE-Final Inspection5/2/20055/3/20055/3/2005 1:40:09 PMAFAIL
Doors to the mechanical rooms did not latch
BLD03-02530 FIRE-Final Inspection5/2/20055/3/20055/3/2005 1:39:47 PMAFAIL
Doors to the mechanical rooms did not latch
BLD03-02528 FIRE-Final Inspection5/2/20055/3/20055/3/2005 1:39:25 PMAFAIL
Doors to the mechanical rooms did not latch
BLD03-02529 FIRE-Final Inspection5/2/20055/3/20055/3/2005 1:39:06 PMAFAIL
Doors to the mechanical rooms did not latch
BLD03-02526 FIRE-Final Inspection5/2/20055/3/20055/3/2005 1:38:49 PMAFAIL
Doors to the mechanical rooms did not latch
BLD03-02527 FIRE-Final Inspection5/2/20055/3/20055/3/2005 1:38:15 PMAFAIL
Door to apartment 101 did not close and neither did the mechanical room doors.
BLD04-01039 FIRE-Final Inspection5/2/20055/3/20055/3/2005 12:42:54 PMAPASS
Fire life safety finaled. Inspection was to finish out this permit. Per Todd with Peak Electric the emergency lights are attached to the emergency generator and have been tested.
FIR04-00656 INSP-Final Inspection5/2/20055/3/20055/3/2005 11:46:23 AMAFAIL
Not ready for final yet.
FIR04-00656 INSP-Sprinkler Rough-in/Hydro5/2/20055/3/20055/3/2005 11:45:47 AMAPASS
I verified that the past deficiencies have been corrected. Need verification that the underground flush has been done.
FIR05-00068 INSP-Sprinkler Rough-in5/3/20055/3/20055/3/2005 11:25:43 AMPPART
Sprinkler piping for room 137 is ok to cover. Looked at the eq bracing for the north half of building. It looks ok.
FIR05-00161 INSP-Final Inspection5/2/20055/3/20055/3/2005 10:07:33 AMAPASS
Fire sprinkler finaled
FIR04-00790 INSP-Final Inspection4/28/20055/3/20055/3/2005 10:01:09 AMAFAIL
No test performed due to the electrical switches located under the hood do not shut off upon activation of hood suppression system. The system installer notified me of this.
BLD05-00007 FIRE-Final Inspection5/3/20055/3/20055/3/2005 9:50:18 AMAPASS
Fire life safety finaled
FIR04-00590 INSP-Final Inspection4/29/20055/3/20055/3/2005 9:48:10 AMAPASS
fire alarm finaled
FIR05-00188 INSP-Final Inspection4/29/20055/3/20055/3/2005 9:47:14 AMAPASS
fire alarm finaled
FIR05-00232 INSP-Final Inspection4/29/20055/3/20055/3/2005 9:45:44 AMAPASS
fire alarm finaled
FIR04-00656 INSP-Sprinkler Rough-in/Hydro5/3/20055/3/20055/3/2005 12:00:00 AMPPART
2nd, 3rd and 4th floor hydro tests passed