FIR06-00245
| INSP-Alarm Testing | 5/3/2006 | 5/3/2006 | 5/4/2006 9:14:52 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 5/3/2006 at 9:01:50 AM. Contact: ###-####.
|
FIR05-00881
| INSP-Sprinkler Rough-in | 5/2/2006 | 5/3/2006 | 5/3/2006 3:38:06 PM | P | PART |
|
|
Partial inspection for the 1st floor SW side overhead piping rough-in, need to provide vertical restraint for heads at arm-overs with ATR/ring hangers, provide protection below stairs, watch surface mounted obstructions that may develop due to close proximity of pendent heads and junction boxes at some locations, no plumbing pipe is allowed to be supported by fire sprinkler pipe.
|
BLD05-02358
| FIRE-Final Inspection | 5/3/2006 | 5/3/2006 | 5/3/2006 2:49:51 PM | A | FAIL |
|
|
The project related sprinkler permit has not been requested for final inspection.
|
BLD06-00597
| FIRE-Final Inspection | 5/3/2006 | 5/3/2006 | 5/3/2006 2:38:50 PM | P | PASS |
|
|
Fire life safety inspection passed.
|
MIS06-00081
| FIR-Final | 5/2/2006 | 5/3/2006 | 5/3/2006 2:15:05 PM | P | PASS |
|
|
Life safety is satisfactory, items on previous correction notice have been completed.
|
FIR05-00710
| INSP-Sprinkler Rough-in/Hydro | 5/1/2006 | 5/3/2006 | 5/1/2006 8:36:02 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 5/1/2006 at 8:32:15 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on May 1 2006 8:36AM.
|