BLD08-00264
| FIRE-Final Inspection | 4/28/2010 | 4/29/2010 | | A | |
|
|
Jim Phone #: ###-####
|
FIR10-00153
| INSP-Final Inspection | 5/3/2010 | 5/3/2010 | 5/3/2010 6:31:45 PM | P | PASS |
|
|
Scope of fire sprinkler work passed final inspection.
|
FIR10-00177
| INSP-Sprinkler Rough-in | 5/3/2010 | 5/3/2010 | 5/3/2010 6:30:50 PM | P | PART |
|
|
Overhead fire sprinkler system modifications approved for cover at the drop ceilings.
|
FIR09-00486
| INSP-Final Inspection | 5/3/2010 | 5/3/2010 | 5/3/2010 6:28:51 PM | P | PASS |
|
|
Underground fire supply line permit okay for final status.
|
BLD10-00765
| FIRE-Final Inspection | 5/3/2010 | 5/3/2010 | 5/3/2010 6:27:17 PM | P | PASS |
|
|
Correction items finished, fire life safety finaled.
|
BLD10-00662
| FIRE-Final Inspection | 5/3/2010 | 5/3/2010 | 5/3/2010 6:26:26 PM | P | PASS |
|
|
Fire life safety inspection passed, door hardware installed while on site.
|
BLD09-00145
| FIRE-Final Inspection | 5/3/2010 | 5/3/2010 | 5/3/2010 6:24:20 PM | A | FAIL |
|
|
Refer to fire code review note item #19, discussed knox box installation and remainder of issues for final.
|
FIR09-00540
| INSP-Final Inspection | 4/30/2010 | 5/3/2010 | 5/3/2010 6:20:30 PM | A | PART |
|
|
See plan review comments regarding control valve operations at post indicators or provision for a one hour rated riser room. Forward flow completed satisfactory.
|
FIR10-00057
| INSP-Final Inspection | 4/29/2010 | 5/3/2010 | 5/3/2010 5:59:49 PM | A | PART |
|
|
Final pending items including signage at the door the to FACP room, knox box install, hat flash in the elevator car upon SD or HD activation in the hoistway or machine room, pending drop ceiling install at the mechanical/electrical room or the addition of a post indicator valve for the fire sprinkler system may require field modifications to the alarm system. Remainder of FA work passed inspection.
|
BLD10-00385
| FIRE-Final Inspection | 5/3/2010 | 5/3/2010 | 5/3/2010 2:34:56 PM | P | PASS |
|
|
Noted correction items field verified for completion, life safety passed.
|
FIR10-00189
| INSP-Final Inspection | 5/3/2010 | 5/3/2010 | 5/3/2010 2:33:32 PM | A | PASS |
|
|
Fire life safety final approved.
|
BLD10-00782
| FIRE-Final Inspection | 4/30/2010 | 5/3/2010 | 5/3/2010 2:32:55 PM | A | PASS |
|
|
Fire sprinkler permit finaled, inspection passed.
|