Inspections for the day of: Monday, May 3, 2010.
Number of inspections: 12
Percentage of inspections complete: 92 %
Percentage of inspections not complete: 8 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-00264 FIRE-Final Inspection4/28/20104/29/2010 A 
Jim Phone #: ###-####
FIR10-00153 INSP-Final Inspection5/3/20105/3/20105/3/2010 6:31:45 PMPPASS
Scope of fire sprinkler work passed final inspection.
FIR10-00177 INSP-Sprinkler Rough-in5/3/20105/3/20105/3/2010 6:30:50 PMPPART
Overhead fire sprinkler system modifications approved for cover at the drop ceilings.
FIR09-00486 INSP-Final Inspection5/3/20105/3/20105/3/2010 6:28:51 PMPPASS
Underground fire supply line permit okay for final status.
BLD10-00765 FIRE-Final Inspection5/3/20105/3/20105/3/2010 6:27:17 PMPPASS
Correction items finished, fire life safety finaled.
BLD10-00662 FIRE-Final Inspection5/3/20105/3/20105/3/2010 6:26:26 PMPPASS
Fire life safety inspection passed, door hardware installed while on site.
BLD09-00145 FIRE-Final Inspection5/3/20105/3/20105/3/2010 6:24:20 PMAFAIL
Refer to fire code review note item #19, discussed knox box installation and remainder of issues for final.
FIR09-00540 INSP-Final Inspection4/30/20105/3/20105/3/2010 6:20:30 PMAPART
See plan review comments regarding control valve operations at post indicators or provision for a one hour rated riser room. Forward flow completed satisfactory.
FIR10-00057 INSP-Final Inspection4/29/20105/3/20105/3/2010 5:59:49 PMAPART
Final pending items including signage at the door the to FACP room, knox box install, hat flash in the elevator car upon SD or HD activation in the hoistway or machine room, pending drop ceiling install at the mechanical/electrical room or the addition of a post indicator valve for the fire sprinkler system may require field modifications to the alarm system. Remainder of FA work passed inspection.
BLD10-00385 FIRE-Final Inspection5/3/20105/3/20105/3/2010 2:34:56 PMPPASS
Noted correction items field verified for completion, life safety passed.
FIR10-00189 INSP-Final Inspection5/3/20105/3/20105/3/2010 2:33:32 PMAPASS
Fire life safety final approved.
BLD10-00782 FIRE-Final Inspection4/30/20105/3/20105/3/2010 2:32:55 PMAPASS
Fire sprinkler permit finaled, inspection passed.