Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-01304 FIRE-Final Inspection5/3/20105/3/20105/3/2010 4:01:51 PMPFAIL
All items are complete except for the two exit signs at the mechanical room.
FIR09-00112 INSP-Final Inspection5/3/20105/3/20105/3/2010 3:45:46 PMPCANC
Cancelled due to time constraints. Rescheduled for tomorrow.
FIR09-00551 INSP-Final Inspection5/3/20105/3/20105/3/2010 3:02:59 PMPFAIL
The hvac units apparently have not been connected for shutdown upon alarm activation. Supposedly will be wired/connected tomorrow and the inspection will be called back in. Re-inspection fee applied. A re-inspection fee was applied previously as well.
BLD10-00545 FIRE-Final Inspection5/3/20105/3/20105/3/2010 2:59:06 PMPPASS
Life safety passed.
FIR09-00010 INSP-Final Inspection5/3/20105/3/20105/3/2010 1:42:39 PMPPASS
Permit finaled
BLD10-00087 FIRE-Final Inspection5/3/20105/3/20105/3/2010 11:36:06 AMPPASS
Life safety passed.
BLD10-00875 FIRE-Final Inspection4/30/20105/3/20105/3/2010 11:25:46 AMAFAIL
Repair all exit signs and emergency lights, repair the non operational fire alarm system, provide annual inspection for the fire sprinkler system and provide missing canopies for the sprinkler pendants.
FIR10-00197 INSP-Final Inspection4/30/20105/3/20105/3/2010 9:41:16 AMAPASS
Permit finaled
FIR10-00016 INSP-Alarm Testing4/30/20105/3/20105/3/2010 9:40:56 AMAFAIL
Provide resubmittals that reflect the correct model of AES installed with the intellitap, provide correct size of battery and provide the map for the facp. The netcon was verified at 5. No alarm, trouble or supervisiory signals were verified.