BLD08-01304
| FIRE-Final Inspection | 5/3/2010 | 5/3/2010 | 5/3/2010 4:01:51 PM | P | FAIL |
|
|
All items are complete except for the two exit signs at the mechanical room.
|
FIR09-00112
| INSP-Final Inspection | 5/3/2010 | 5/3/2010 | 5/3/2010 3:45:46 PM | P | CANC |
|
|
Cancelled due to time constraints. Rescheduled for tomorrow.
|
FIR09-00551
| INSP-Final Inspection | 5/3/2010 | 5/3/2010 | 5/3/2010 3:02:59 PM | P | FAIL |
|
|
The hvac units apparently have not been connected for shutdown upon alarm activation. Supposedly will be wired/connected tomorrow and the inspection will be called back in. Re-inspection fee applied. A re-inspection fee was applied previously as well.
|
BLD10-00545
| FIRE-Final Inspection | 5/3/2010 | 5/3/2010 | 5/3/2010 2:59:06 PM | P | PASS |
|
|
Life safety passed.
|
FIR09-00010
| INSP-Final Inspection | 5/3/2010 | 5/3/2010 | 5/3/2010 1:42:39 PM | P | PASS |
|
|
Permit finaled
|
BLD10-00087
| FIRE-Final Inspection | 5/3/2010 | 5/3/2010 | 5/3/2010 11:36:06 AM | P | PASS |
|
|
Life safety passed.
|
BLD10-00875
| FIRE-Final Inspection | 4/30/2010 | 5/3/2010 | 5/3/2010 11:25:46 AM | A | FAIL |
|
|
Repair all exit signs and emergency lights, repair the non operational fire alarm system, provide annual inspection for the fire sprinkler system and provide missing canopies for the sprinkler pendants.
|
FIR10-00197
| INSP-Final Inspection | 4/30/2010 | 5/3/2010 | 5/3/2010 9:41:16 AM | A | PASS |
|
|
Permit finaled
|
FIR10-00016
| INSP-Alarm Testing | 4/30/2010 | 5/3/2010 | 5/3/2010 9:40:56 AM | A | FAIL |
|
|
Provide resubmittals that reflect the correct model of AES installed with the intellitap, provide correct size of battery and provide the map for the facp. The netcon was verified at 5. No alarm, trouble or supervisiory signals were verified.
|