Inspections for the day of: Tuesday, May 3, 2011.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-02086 ELE-Aging Inspection5/3/20115/3/20115/4/2011 7:30:54 AM DONE
still under construction
ELE10-01984 ELE-Aging Inspection5/3/20115/3/20115/4/2011 7:27:45 AM DONE
still under construction
ELE11-00867 Temporary Service5/3/20115/3/20115/3/2011 3:36:33 PMPCANC
Alan Phone #: ###-#### contractor called, not ready
ELE11-00866 Temporary Service5/3/20115/3/20115/3/2011 3:35:59 PMPCANC
Alan Phone #: ###-#### contractor called, not ready
ELE11-00311 Final5/3/20115/3/20115/3/2011 3:11:58 PMPPASS
Should be open if not garage code is JAYO enter Phone #: ###-#### >> Inspection requested via web by Zane Robertson ok to final
ELE11-00606 Final5/3/20115/3/20115/3/2011 1:51:09 PMPCANC
please pull up roll up garage door. Thank you and please call if you have any questions Phone #: ###-#### >> Inspection requested via web by Steve Ruter wet concrete, called to re-schedule
ELE11-00184 Final5/3/20115/3/20115/3/2011 1:00:04 PMPPASS
ok final
ELE11-00873 Temporary Service5/3/20115/3/20115/3/2011 12:37:53 PMPPASS
Overhead temp pole at Northeast corner of property. Contact is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery t/s o/h n ok
ELE11-00851 Rough-In Permanent Service5/3/20115/3/20115/3/2011 10:31:52 AMAPASS
Call Dene with any questions. Thank you Phone #: ###-#### >> Inspection requested via web by kim grundhauser ri ok, p/s u/g n ok
ELE11-00867 Temporary Service5/2/20115/3/20115/3/2011 9:46:07 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Alan Lusk called, left correction notice, NEC 250.53(G) shall drive in ground rod until flush with or below ground
ELE11-00866 Temporary Service5/2/20115/3/20115/3/2011 9:09:00 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Alan Lusk called, left correction notice, NEC 250.92 shall provide bond bushing, 110.26, shall provide work space for depth, 250.53(G) shall drive in ground rod
ELE11-00447 Final5/2/20115/3/20115/3/2011 8:52:25 AMAFAIL
GARAGE CODE 1968 Phone #: ###-#### >> Inspection requested via web by Bob Glenn called, short in garage ,outside circuits, will fix and recall
ELE11-00861 Final5/2/20115/3/20115/3/2011 8:26:26 AMAPASS
Inspection on wiring for A/C unit, any questions call Jake @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose ok final
ELE11-00866 Final5/2/20115/3/20115/2/2011 3:54:36 PMACANC
Phone #: ###-#### >> Inspection requested via web by Alan Lusk Inspection cancelled from web by: Alan Lusk