FIR09-00645
| INSP-Conference | 4/27/2012 | 4/27/2012 | | A | |
|
|
Contact Brian M.
|
BLD12-00197
| FIRE-Final Inspection | 4/3/2012 | 5/3/2012 | 5/4/2012 12:13:41 PM | A | PASS |
|
|
Final fire life safety inspection passed. Noted correction items have been finished.
|
BLD12-00553
| FIRE-Final Inspection | 5/3/2012 | 5/3/2012 | 5/4/2012 6:54:09 AM | P | PASS |
|
|
Fire life safety passed pending thumbturn locks at the office and conference room slider doors are removed or replaced with approved style hardware as discussed. To be finished prior to structural final inspection.
|
FIR12-00133
| INSP-Sprinkler Rough-in | 5/3/2012 | 5/3/2012 | 5/4/2012 6:51:39 AM | P | PART |
|
|
Verified plan modification work. Basement rough-in only okayed for cover. Discussed cold cavity protection issues at the first floor and underground fire supply line work that appears to have been completed without an associated FIR permit or inspection for cover.
|
FIR11-00574
| INSP-Final Inspection | 5/2/2012 | 5/3/2012 | 5/3/2012 1:54:56 PM | P | NH |
|
|
Please call Randy 15-20 minutes prior to inspection. Thanks Phone #: ###-#### >> Inspection requested via web by Mark Sessions ** Arrived on site and met contractor, no access could be provided to complete a re-inspection **
|
BLD11-03041
| FIRE-Final Inspection | 5/3/2012 | 5/3/2012 | 5/3/2012 1:52:54 PM | A | FAIL |
|
|
Noted items include; missing exit signs per approved plan, door holders per sheet E2 are not yet installed, missing ceiling tile and escutcheons adjacent to the new type one hood. A fire alarm permit will be necessary to complete door holder and smoke detection work. Project related fire sprinkler permit needs request for inspection and final. See attatched fire code review notes for details.
|
FIR12-00203
| INSP-Supply line flush | 5/3/2012 | 5/3/2012 | 5/3/2012 1:48:42 PM | P | PART |
|
|
UG fire supply line flush completed satisfactory.
|
FIR12-00200
| INSP-Final Inspection | 5/3/2012 | 5/3/2012 | 5/3/2012 1:08:35 PM | A | PASS |
|
|
Permit finaled.
|
FIR12-00200
| INSP-Sprinkler Rough-in | 5/3/2012 | 5/3/2012 | 5/3/2012 1:07:34 PM | A | PART |
|
|
Hood suppression system operated correctly under test conditions.
|
FIR12-00203
| INSP-Sprinkler Rough-in | 5/2/2012 | 5/3/2012 | 5/3/2012 1:01:41 PM | A | PART |
|
|
UG fire supply line approved for bury. Discussed bedding material install with contractor.
|
BLD11-02675
| FIRE-Final Inspection | 5/2/2012 | 5/3/2012 | 5/3/2012 12:56:25 PM | A | FAIL |
|
|
Correction items include; post "door to remain unlocked while building is occupied" sign at the main entry/exit, provide single action hardware at the back exit per plan review annotations, repair exit sign/ emergency light above the back exit door. Also noted existing fire sprinkler coverage is overspaced off adjacent walls at the office and main lobby areas (three locations). Partition walls do not appear to have been included in the original design and constructed without permit at a later date. Any modifications to an existing fire sprinkler system will require a separate permit and be completed by a state licensed contractor. See plan notes and permit card for details.
|