ELE16-03933
| Electrical Rough-In | 5/2/2017 | 5/3/2017 | 5/3/2017 3:32:39 PM | P | PASS |
|
|
Rough- in walls only in 2nd floor. Management office 210, corridor 211, elevator lobby 201, business center 202, corridor 208, fitness center 203, bike parking 213, restrooms 204 ; 205, dog wash 216. Contact Fabian Luna Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted plus parcel room as noted on print in general contractors trailer wall rough in ok cover.
|
ELE17-01286
| Permanent Service | 5/3/2017 | 5/3/2017 | 5/3/2017 2:33:00 PM | P | FAIL |
|
|
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden 110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied. 110.24- Available fault current shall be posted prior to permenant service inspection. 250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed. 250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed. 250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system. 250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
|
ELE17-01284
| Permanent Service | 5/3/2017 | 5/3/2017 | 5/3/2017 2:32:34 PM | P | FAIL |
|
|
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden 110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied. 110.24- Available fault current shall be posted prior to permenant service inspection. 250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed. 250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed. 250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system. 250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
|
ELE17-01285
| Permanent Service | 5/3/2017 | 5/3/2017 | 5/3/2017 2:31:54 PM | P | FAIL |
|
|
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden 110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied. 110.24- Available fault current shall be posted prior to permenant service inspection. 250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed. 250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed. 250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system. 250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
|
ELE17-01299
| Permanent Service | 5/3/2017 | 5/3/2017 | 5/3/2017 2:31:15 PM | P | FAIL |
|
|
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden 110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied. 110.24- Available fault current shall be posted prior to permenant service inspection. 250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed. 250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed. 250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system. 250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
|
ELE17-01297
| Permanent Service | 5/3/2017 | 5/3/2017 | 5/3/2017 2:30:33 PM | P | FAIL |
|
|
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden 110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied. 110.24- Available fault current shall be posted prior to permenant service inspection. 250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed. 250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed. 250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system. 250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
|
ELE17-01301
| Permanent Service | 5/3/2017 | 5/3/2017 | 5/3/2017 2:29:59 PM | P | FAIL |
|
|
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden 110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied. 110.24- Available fault current shall be posted prior to permenant service inspection. 250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed. 250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed. 250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system. 250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
|
ELE17-01289
| Permanent Service | 5/3/2017 | 5/3/2017 | 5/3/2017 2:29:25 PM | P | FAIL |
|
|
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden 110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied. 110.24- Available fault current shall be posted prior to permenant service inspection. 250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed. 250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed. 250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system. 250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
|
ELE17-01287
| Permanent Service | 5/3/2017 | 5/3/2017 | 5/3/2017 2:28:48 PM | P | FAIL |
|
|
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden 110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied. 110.24- Available fault current shall be posted prior to permenant service inspection. 250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed. 250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed. 250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system. 250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
|
ELE17-01288
| Permanent Service | 5/3/2017 | 5/3/2017 | 5/3/2017 2:28:00 PM | P | FAIL |
|
|
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden 110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied. 110.24- Available fault current shall be posted prior to permenant service inspection. 250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed. 250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed. 250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system. 250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
|
ELE17-01290
| Permanent Service | 5/3/2017 | 5/3/2017 | 5/3/2017 2:27:06 PM | P | FAIL |
|
|
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden 110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied. 110.24- Available fault current shall be posted prior to permenant service inspection. 250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed. 250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed. 250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system. 250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
|
ELE17-01320
| Electrical Rough-In | 5/3/2017 | 5/3/2017 | 5/3/2017 2:00:04 PM | P | PASS |
|
|
THIS REQUEST IS FOR UNDERGROUND READY TO COVER
Please contact Tate with any questions or concerns @ ###-####
Thank you and have a great day! Phone #: ###-#### Inspection requested via web by JENNY EMEL Back area to be covered by an elevated deck creating 3' to 5' depth on underground. Rough in ok cover
|
ELE99-03777
| Final | 4/27/2017 | 5/3/2017 | 5/3/2017 12:40:28 PM | P | PASS |
|
|
Keenan Phone #: ###-#### Unable to check all due to furniture in place. Final ok
|
ELE99-03740
| Final | 4/27/2017 | 5/3/2017 | 5/3/2017 12:39:38 PM | P | PASS |
|
|
Keenan Phone #: ###-#### Unable to check all due to furniture in place. Final ok
|
ELE17-01295
| Temporary Service | 5/2/2017 | 5/3/2017 | 5/3/2017 11:29:49 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by steve cooper t/s u/g n ok
|
ELE17-00037
| Final | 5/2/2017 | 5/3/2017 | 5/3/2017 10:49:12 AM | A | PART |
|
|
Final for Units 513 and 613 Contact Dan Hutchinson Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted TCO OK
|
ELE16-01667
| Electrical Rough-In | 5/2/2017 | 5/3/2017 | 5/3/2017 10:10:32 AM | A | PASS |
|
|
Garden Shed and drop ceiling 305 Suite and 307 amenities Phone #: ###-#### Inspection requested via web by Tom Betty Garden shed wiring must be covered prior to weater. Rough in ok cover
|
ELE17-01306
| Rough-In Permanent Service | 5/2/2017 | 5/3/2017 | 5/3/2017 9:37:17 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk Dupicate request Rough in ok cover p/s u/g n ok
|
ELE17-01306
| Rough-In Permanent Service | 5/2/2017 | 5/3/2017 | 5/3/2017 9:36:28 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk Rough in ok cover p/s u/g n ok
|