Inspections for the day of: Wednesday, May 3, 2017.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-03933 Electrical Rough-In5/2/20175/3/20175/3/2017 3:32:39 PMPPASS
Rough- in walls only in 2nd floor. Management office 210, corridor 211, elevator lobby 201, business center 202, corridor 208, fitness center 203, bike parking 213, restrooms 204 ; 205, dog wash 216.
Contact Fabian Luna
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
Rooms noted plus parcel room as noted on print in general contractors trailer wall rough in ok cover.
ELE17-01286 Permanent Service5/3/20175/3/20175/3/2017 2:33:00 PMPFAIL
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden
110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied.
110.24- Available fault current shall be posted prior to permenant service inspection.
250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed.
250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed.
250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system.
250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
ELE17-01284 Permanent Service5/3/20175/3/20175/3/2017 2:32:34 PMPFAIL
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden
110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied.
110.24- Available fault current shall be posted prior to permenant service inspection.
250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed.
250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed.
250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system.
250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
ELE17-01285 Permanent Service5/3/20175/3/20175/3/2017 2:31:54 PMPFAIL
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden
110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied.
110.24- Available fault current shall be posted prior to permenant service inspection.
250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed.
250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed.
250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system.
250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
ELE17-01299 Permanent Service5/3/20175/3/20175/3/2017 2:31:15 PMPFAIL
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden
110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied.
110.24- Available fault current shall be posted prior to permenant service inspection.
250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed.
250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed.
250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system.
250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
ELE17-01297 Permanent Service5/3/20175/3/20175/3/2017 2:30:33 PMPFAIL
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden
110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied.
110.24- Available fault current shall be posted prior to permenant service inspection.
250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed.
250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed.
250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system.
250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
ELE17-01301 Permanent Service5/3/20175/3/20175/3/2017 2:29:59 PMPFAIL
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden
110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied.
110.24- Available fault current shall be posted prior to permenant service inspection.
250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed.
250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed.
250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system.
250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
ELE17-01289 Permanent Service5/3/20175/3/20175/3/2017 2:29:25 PMPFAIL
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden
110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied.
110.24- Available fault current shall be posted prior to permenant service inspection.
250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed.
250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed.
250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system.
250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
ELE17-01287 Permanent Service5/3/20175/3/20175/3/2017 2:28:48 PMPFAIL
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden
110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied.
110.24- Available fault current shall be posted prior to permenant service inspection.
250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed.
250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed.
250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system.
250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
ELE17-01288 Permanent Service5/3/20175/3/20175/3/2017 2:28:00 PMPFAIL
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden
110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied.
110.24- Available fault current shall be posted prior to permenant service inspection.
250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed.
250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed.
250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system.
250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
ELE17-01290 Permanent Service5/3/20175/3/20175/3/2017 2:27:06 PMPFAIL
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden
110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied.
110.24- Available fault current shall be posted prior to permenant service inspection.
250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed.
250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed.
250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system.
250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
ELE17-01320 Electrical Rough-In5/3/20175/3/20175/3/2017 2:00:04 PMPPASS
THIS REQUEST IS FOR UNDERGROUND READY TO COVER

Please contact Tate with any questions or concerns @ ###-####

Thank you and have a great day! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Back area to be covered by an elevated deck creating 3' to 5' depth on underground. Rough in ok cover
ELE99-03777 Final4/27/20175/3/20175/3/2017 12:40:28 PMPPASS
Keenan Phone #: ###-####
Unable to check all due to furniture in place.
Final ok
ELE99-03740 Final4/27/20175/3/20175/3/2017 12:39:38 PMPPASS
Keenan Phone #: ###-####
Unable to check all due to furniture in place. Final ok
ELE17-01295 Temporary Service5/2/20175/3/20175/3/2017 11:29:49 AMAPASS
Phone #: ###-#### Inspection requested via web by steve cooper t/s u/g n ok
ELE17-00037 Final5/2/20175/3/20175/3/2017 10:49:12 AMAPART
Final for Units 513 and 613
Contact Dan Hutchinson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Rooms noted TCO OK
ELE16-01667 Electrical Rough-In5/2/20175/3/20175/3/2017 10:10:32 AMAPASS
Garden Shed and drop ceiling 305 Suite and 307 amenities Phone #: ###-#### Inspection requested via web by Tom Betty
Garden shed wiring must be covered prior to weater. Rough in ok cover
ELE17-01306 Rough-In Permanent Service5/2/20175/3/20175/3/2017 9:37:17 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk Dupicate request
Rough in ok cover p/s u/g n ok
ELE17-01306 Rough-In Permanent Service5/2/20175/3/20175/3/2017 9:36:28 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g n ok