ELE18-01295
| Electrical Rough-In | 5/3/2018 | 5/3/2018 | 5/3/2018 2:38:35 PM | P | PASS |
|
|
please call when on way to meet // Jose Phone #: ###-#### Furniture north side only and grid north and east only rough in ok cover
|
ELE18-01636
| Final | 5/3/2018 | 5/3/2018 | 5/3/2018 1:46:44 PM | P | PASS |
|
|
please call Max @ ###-#### an he will meet Phone #: ###-#### Inspection requested via web by dennis mcneely Final ok
|
ELE18-01677
| Electrical Rough-In | 5/3/2018 | 5/3/2018 | 5/3/2018 1:46:05 PM | P | FAIL |
|
|
Walls inspection. Please contact owner, Nick at ###-#### to give a heads up when heading to location. Phone #: ###-#### Inspection requested via web by Dean Gernaat BLD states no work under this permit. Contacted Dave Hanna about a wood wall elevated for menu boards, He stated this needs looked at prior to determine if additional permits needed. Recall when complete.
|
ELE18-01680
| Electrical Rough-In | 5/3/2018 | 5/3/2018 | 5/3/2018 1:17:27 PM | P | PASS |
|
|
Grounding inspection -contact is Derek Ball Phone #: ###-#### Inspection requested via web by Scott Campbell Pole bases only located in alley between 8th and 9th street. Base pour rough in ok cover
|
ELE18-00727
| Electrical Rough-In | 5/2/2018 | 5/3/2018 | 5/3/2018 11:35:56 AM | A | PART |
|
|
Wall inspections Phone #: ###-#### Inspection requested via web by Tom Jenkins Bread room, serving window area, back house, bathroom walls noted rough in ok cover
|
ELE17-01337
| Electrical Rough-In | 5/2/2018 | 5/3/2018 | 5/3/2018 11:34:00 AM | A | PART |
|
|
We are requesting a partial final for the 2nd floor guest rooms for tomorrow morning. Our contact is Rick @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate 228 not ready, 201 thru 204 and 209 thru 211 furniture covering receptacles. Remove for inspection. 205 thru 208 and 212 thru 234 ok for funiture.
|
ELE18-01221
| Final | 5/3/2018 | 5/3/2018 | 5/3/2018 10:40:12 AM | A | FAIL |
|
|
first floor elevator vestibule. front or back door will be open. please call chase with questions. ###-#### Phone #: ###-#### Inspection requested via web by Cyndi Dale 300.15- All wiring shall terminate in box. Elevator corridor and entrance covers complete, vanilla space to east which had work associated with remodel has several open boxes and MC not terminated in boxes with stripped wires hanging out exposed. Safe off all wiring in vanilla space. BCC 04-05-32 code violations not to be retained.
|
ELE18-01674
| Rough-In Permanent Service | 5/2/2018 | 5/3/2018 | 5/3/2018 10:03:59 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Robert Murray 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing suface they shall be protected from damage by nail plates. Garage 10-2 rt of panel, above garage switches, above pantry switch, entry corner. 300.15- Wall wiring shall terminate in a box. Master stool bath fan not made up.
|
ELE18-00968
| Final | 5/2/2018 | 5/3/2018 | 5/3/2018 9:06:45 AM | A | FAIL |
|
|
garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn 210.52(A)- No point along floor line shall be more than 6' from a receptacle outlet. Family room east wall no receptacle with in 6' of start of wall, 1st receptacle 9' of start.
|
ELE18-01221
| Final | 5/2/2018 | 5/3/2018 | 5/3/2018 6:59:37 AM | A | CANC |
|
|
please call Chase with any questions - ###-#### Phone #: ###-#### >> Inspection requested via web by Cyndi Dale Inspection cancelled from web by: Cyndi Dale
|
MIS18-00159
| ELE-Conference | 5/2/2018 | 5/3/2018 | 5/2/2018 2:46:05 PM | A | PASS |
|
|
licensed contractor repairing existing post light wiring, damaged by shovel. No permit required
|