Inspections for the day of: Thursday, May 3, 2018.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-00750 Final5/3/20185/3/20185/3/2018 4:26:39 PMPFAIL
Garage code #1234 Phone #: ###-#### Inspection requested via web by Debbie Marino
- Need Man J and Air balance reports onsite
MEC18-00847 Final5/3/20185/3/20185/3/2018 3:53:52 PMPPASS
Garage code #1234 Phone #: ###-#### Inspection requested via web by Debbie Marino
- Final ok
MEC18-01926 Pressure Test5/1/20185/3/20185/3/2018 3:22:58 PMPNH
INSTALLER ANAS ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- no access for pressure test
MEC18-01782 Rough-in5/3/20185/3/20185/3/2018 3:21:14 PMPPART
Phone #: ###-#### Inspection requested via web by Dan Otero- partial R/I- venting ok- builder needs to cover up some holes in the wall behind fireplace
MEC18-01948 Final5/2/20185/3/20185/3/2018 2:35:10 PMPPASS
PM / Please cal the technician when on way ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- furnace ac coil co ok
MEC18-01955 Rough-in5/3/20185/3/20185/3/2018 1:56:19 PMPPASS
MEC AND FIREPL Phone #: ###-#### Inspection requested via web by Oleg Chervak-R/I ok
MEC18-01955 Pressure Test5/3/20185/3/20185/3/2018 1:51:46 PMPFAIL
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20 lb gas fail gauge was under 20 lbs
MEC18-01732 Rough-in5/3/20185/3/20185/3/2018 1:18:36 PMPPASS
Phone #: ###-#### Inspection requested via web by Debbie Marino- Dryer vent framing is ok- flue pressure test ok- R/I ok
MEC18-01936 Final5/3/20185/3/20185/3/2018 12:40:34 PMPPASS
PLEASE schedule for mid-afternoon if possible.
Contact JR: ###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello- furnace ac coil co ok
MEC18-00365 Final5/2/20185/3/20185/3/2018 11:58:56 AMPFAIL
Phone #: ###-#### Inspection requested via web by Oleg Chervak
unti 101- lineset in mech room needs insulation,taped, and supported- indoor unit needs braced to wall/supported-need duct blast and air balance reports onsite
unit 102- lineset in mech room needs insulated and supported- fresh air ducts need insulated- need duct blast and air balance reports onsite
unit 103- lineset in mech room needs insulated and supported - lineset at outdoor unit needs UV protection- indoor unit needs to be braced to wall- need duct blast and air balance reports onsite
unit 104- mech room was locked - need duct blast and air balance reports onsite
MEC18-00363 Final5/2/20185/3/20185/3/2018 11:52:19 AMPFAIL
Phone #: ###-#### Inspection requested via web by Oleg Chervak
unit 101- lineset on indoor unit needs insulation and supported- needs duct blast and airbalance reports on site
unit 102- lineset on indoor unit needs taped- fresh air in the mech room needs insulated- needs duct blast and air balance reports onsite
unit 103- need duct blast and air balnce reports onsite
unit 104- fresh air in mech room to insulated- need duct blast and air balance reports onsite
MEC18-01847 Final5/2/20185/3/20185/3/2018 10:44:07 AMAPASS
can you please call when you are on the way so someone can give you access. customers name is Willard ###-#### Phone #: ###-#### Inspection requested via web by Marisa Hone- furnace ac coil co ok
MEC18-00673 Final5/2/20185/3/20185/3/2018 10:13:10 AMAPASS
Final inspection. Francisco is your contact Phone #: ###-#### Inspection requested via web by Kim Adams- final ok
MEC16-01564 Mec-Aging Inspection5/3/20185/3/20185/3/2018 10:09:43 AM NH
not home- left notice on front door
MEC18-01910 Final5/3/20185/3/20185/3/2018 9:27:38 AMPPASS
Phone #: ###-#### Inspection requested via web by Devony Bullard- plumbing permit for the water was pulled
MEC18-01925 Final5/1/20185/3/20185/1/2018 11:39:19 AMPCANC
PLEASE CALL LEAD INSTALLER BRAD WHEN 30 MINS IN ROUTE. LATER AFTERNOON WOULD BE PREFERRED IF POSSIBLE, 3-5P Phone #: ###-#### >> Inspection requested via web by Rick Montgomery Inspection cancelled from web by: Rick Montgomery