FIR03-00068
| INSP-Sprinkler Rough-in/Hydro | 5/27/2003 | 5/30/2003 | 5/30/2003 12:00:00 AM | A | PASS |
|
|
I gave approval to cover area "A" on the 1st, 2nd and the 3rd floors. The south side 3rd floor 1" and 1 1/4" piping is not tied into the area "B" piping yet. Grooved cplgs at the expansion joints. Walls are not up yet on the third floor but hangers and eq bracing looked ok 5/30/2003 12:44:50 PM
|
BLD02-02855
| FIRE-Final Inspection | 5/28/2003 | 5/30/2003 | 5/30/2003 12:00:00 AM | A | PASS |
|
|
terry; Phone #: ###-#### Fire life safety finaled. Building inspector to verify address has been installed 5/30/2003 12:29:10 PM
|
BLD02-01148
| FIRE-Final Inspection | 5/29/2003 | 5/30/2003 | 5/30/2003 12:00:00 AM | A | FAIL |
|
|
STEVE; Phone #: ###-#### Door hardware has not been changed and the duct smoke detectors did not shut down the hvac units 5/30/2003 9:20:30 AM
|
FIR03-00130
| INSP-Final Inspection | 5/29/2003 | 5/30/2003 | 5/30/2003 12:00:00 AM | A | PASS |
|
|
###-#### cooking hood The hood suppression system for the Outpost Cafe operated correctly 5/30/2003 8:44:50 AM
|
BLD03-00467
| FIRE-Final Inspection | 5/29/2003 | 5/30/2003 | 5/30/2003 12:00:00 AM | A | PASS |
|
|
Life safety finaled. The contractor said that he had an agreement with Carl about the thumbturn on the front door. I notified Carl Dependahl 5/30/2003 3:37:59 PM
|
BLD03-00366
| FIRE-Final Inspection | 5/29/2003 | 5/30/2003 | 5/30/2003 12:00:00 AM | A | PART |
|
|
A temporary occupancy was given with Dave Millers permission since an upgrade agreement has been reached on upgrading the fire alarm system 5/30/2003 2:55:54 PM
|
BLD03-00432
| FIRE-Final Inspection | 5/30/2003 | 5/30/2003 | 5/30/2003 12:00:00 AM | A | FAIL |
|
|
Provide approved fire sprinkle and fire alarm plans, provide approved door hardware, provide fire extinguishers 5/30/2003 12:39:49 PM
|
FIR03-00071
| INSP-Supply line flush | 5/30/2003 | 5/30/2003 | 5/30/2003 12:00:00 AM | P | PASS |
|
|
Supply line flushed 5/30/2003 3:46:07 PM
|
BLD03-00037
| FIRE-Final Inspection | 5/30/2003 | 5/30/2003 | 5/30/2003 12:00:00 AM | P | PASS |
|
|
clint; Phone #: ###-#### Fire life safety finaled 5/30/2003 11:59:00 AM
|
FIR01-00462
| INSP-Sprinkler Rough-in | 5/29/2003 | 5/30/2003 | 5/30/2003 12:00:00 AM | P | PASS |
|
|
mike; Phone #: ###-#### 24 hour air test for the sanctuary dry system is ok. Trip test for this dry pipe riser is ok. Signals went to the monitoring company. Trip time was 1:29. 5/30/2003 1:39:50 PM
|
FIR02-00432
| INSP-Final Inspection | 5/29/2003 | 5/30/2003 | 5/29/2003 3:21:30 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 5/29/2003 at 9:38:27 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on May 29 2003 3:21PM.
|