Inspections for the day of: Friday, May 30, 2003.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00068 INSP-Sprinkler Rough-in/Hydro5/27/20035/30/20035/30/2003 12:00:00 AMAPASS
I gave approval to cover area "A" on the 1st, 2nd and the 3rd floors. The south side 3rd floor 1" and 1 1/4" piping is not tied into the area "B" piping yet. Grooved cplgs at the expansion joints. Walls are not up yet on the third floor but hangers and eq bracing looked ok 5/30/2003 12:44:50 PM
BLD02-02855 FIRE-Final Inspection5/28/20035/30/20035/30/2003 12:00:00 AMAPASS
terry; Phone #: ###-#### Fire life safety finaled. Building inspector to verify address has been installed 5/30/2003 12:29:10 PM
BLD02-01148 FIRE-Final Inspection5/29/20035/30/20035/30/2003 12:00:00 AMAFAIL
STEVE; Phone #: ###-#### Door hardware has not been changed and the duct smoke detectors did not shut down the hvac units 5/30/2003 9:20:30 AM
FIR03-00130 INSP-Final Inspection5/29/20035/30/20035/30/2003 12:00:00 AMAPASS
###-#### cooking hood The hood suppression system for the Outpost Cafe operated correctly 5/30/2003 8:44:50 AM
BLD03-00467 FIRE-Final Inspection5/29/20035/30/20035/30/2003 12:00:00 AMAPASS
Life safety finaled. The contractor said that he had an agreement with Carl about the thumbturn on the front door. I notified Carl Dependahl 5/30/2003 3:37:59 PM
BLD03-00366 FIRE-Final Inspection5/29/20035/30/20035/30/2003 12:00:00 AMAPART
A temporary occupancy was given with Dave Millers permission since an upgrade agreement has been reached on upgrading the fire alarm system 5/30/2003 2:55:54 PM
BLD03-00432 FIRE-Final Inspection5/30/20035/30/20035/30/2003 12:00:00 AMAFAIL
Provide approved fire sprinkle and fire alarm plans, provide approved door hardware, provide fire extinguishers 5/30/2003 12:39:49 PM
FIR03-00071 INSP-Supply line flush5/30/20035/30/20035/30/2003 12:00:00 AMPPASS
Supply line flushed 5/30/2003 3:46:07 PM
BLD03-00037 FIRE-Final Inspection5/30/20035/30/20035/30/2003 12:00:00 AMPPASS
clint; Phone #: ###-#### Fire life safety finaled 5/30/2003 11:59:00 AM
FIR01-00462 INSP-Sprinkler Rough-in5/29/20035/30/20035/30/2003 12:00:00 AMPPASS
mike; Phone #: ###-#### 24 hour air test for the sanctuary dry system is ok. Trip test for this dry pipe riser is ok. Signals went to the monitoring company. Trip time was 1:29. 5/30/2003 1:39:50 PM
FIR02-00432 INSP-Final Inspection5/29/20035/30/20035/29/2003 3:21:30 PMPCANC
Scheduled by a contractor via Hello! on 5/29/2003 at 9:38:27 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on May 29 2003 3:21PM.