ELE06-00102 Final5/30/20065/30/20065/30/2006 4:40:50 PMPFAIL
daniel call to get code; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung corr 410.8 clearence NW BED RM CLOSET FIXTURE, permit #ele06-00102 was used for address 1747 eagleson, and ele05-04584 used for 1741 eagleson, addresses have been messed up from day one called
ELE06-01930 Rough-In Permanent Service5/30/20065/30/20065/30/2006 4:36:55 PMPFAIL
Bill; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr. called 300.4 nail plares and 11/4" random areas both units, 210.52(A) outlet spacing
SW bedrm west unit SE bedrm east unit, only one p/s this is a duplex still not a townhouse
ELE06-01851 Electrical Rough-In5/30/20065/30/20065/30/2006 3:16:05 PMPPASS
Scheduled by a contractor via Hello! on 5/30/2006 at 10:37:21 AM. Contact: ###-####. ok all of basement and upstairs kit,din., bathrm
ELE06-01837 Final5/30/20065/30/20065/30/2006 2:40:37 PMPFAIL
Ron; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt grd rods not 6ft apart he drove the 2nd rod at 45 degrees towards the other grd rod, owner told me the get off his property so I left called Jim S
ELE06-01899 Final5/30/20065/30/20065/30/2006 2:24:24 PMPPASS
Roger; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
ok no card
ELE06-01945 Electrical Rough-In5/30/20065/30/20065/30/2006 2:04:49 PMPPART
POOL BONDING; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok still needs u/g conduit, equip grid, and potting
ELE06-01727 Final5/30/20065/30/20065/30/2006 1:32:43 PMPCANC
Cory; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt see added r/i
ELE06-01727 Electrical Rough-In5/30/20065/30/20065/30/2006 1:31:36 PMPPART
Cory; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt equip. grid ok
ELE05-03535 Final5/30/20065/30/20065/30/2006 1:12:29 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung corr. met owner, 110.14 clockwise wire at screw terminals, 200.11 reversed polarity MB plugs,also needs outlet left of bathrm door over 6ft 210.52(A), 406.3 open grd recepts upstairs bedrm, also no power upstairs hallways314.20 box extensions in paneled walls den, 314.3 shall use non metallic sealtight at W H408.4 panel schedule shall be specific as to location and purpose of circuits 410.14 acess hole required in back of flourescence fixtures garage, 406.4 recepts loose mounting all locations, gfci in kit bad or wiring messed up, shall check all wiring before inspection requested for final too many things wrong
ELE05-02169 Final5/26/20065/30/20065/30/2006 10:19:56 AMAFAIL
Internet Inspection Request from: Latisha Peltier called 314.20 needs box extensions where boxes are not flush with combustible material, 408.4 panel schedules not correct, 210.12 needs afci for bed rms not gfci called contractor will correct and reschedule
ELE06-01866 Conference5/23/20065/30/20065/30/2006 9:30:38 AMADONE
curtis; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok
ELE06-01894 Permanent Service5/24/20065/30/20065/30/2006 8:48:11 AMACANC
###-#### - adam Note: early afternoon asap
called contractor needs pm inspection he will reschedule
ELE06-01898 Rough-In Permanent Service5/26/20065/30/20065/30/2006 8:41:59 AMAPART
Need floor rough-in inspection.; Phone #: ###-#### Internet Inspection Request from: Tina Payne floor west end of bld center section, walked job with contractor looks ok