Inspections for the day of: Tuesday, May 30, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01049 Final5/30/20065/30/20065/30/2006 4:42:22 PMPPASS
please call Mike Dale with any questions; Phone #: ###-#### Internet Inspection Request from: Jeff Radford called left message about 1 recpt plate and outside light not working, ok to final
ELE06-01605 Final5/30/20065/30/20065/30/2006 4:37:58 PMPCANC
TEMP POWER POLE; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy wrong type inspection, should be t/s
ELE06-01605 Temporary Service5/30/20065/30/20065/30/2006 4:37:12 PMPFAIL
TEMP POWER POLE; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy called contr, left corr notice,nec 240.4(D) maximum overcurrent protection for #12 conductor shall be 20A, 352.30 rnc shall be supported within 3' of panel
ELE06-01606 Final5/30/20065/30/20065/30/2006 4:34:04 PMPPASS
TEMP POWER POLE; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy called contr, left survey, nec 312.5 abrasion protection shall be provided for all conductors entering enclosures, t/s u/g n ok should be listed as t/s not final for inspection
ELE06-01193 Electrical Rough-In5/30/20065/30/20065/30/2006 3:41:41 PMPPASS
Larry - interior pool light shells; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt potting only ok
ELE06-01864 Final5/30/20065/30/20065/30/2006 1:54:17 PMPPASS
butch; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt called contrr, looked at relocated panel, recpt, ok to final
ELE06-01954 Electrical Rough-In5/30/20065/30/20065/30/2006 1:12:28 PMPCANC
a-c circuit ###-#### wrong type insp, see final
ELE06-01954 Final5/30/20065/30/20065/30/2006 1:11:57 PMPPASS
a-c circuit ###-#### met elect, told to use pvc coated flex to disc. ok to final
ELE06-00159 Final5/26/20065/30/20065/30/2006 12:23:41 PMACANC
This inspection is for the tile/floor heat.; Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe wrong type inspection
ELE06-01409 Final5/26/20065/30/20065/30/2006 9:57:00 AMAPASS
Scheduled by a contractor via Hello! on 5/26/2006 at 8:22:54 PM. Contact: ###-####. corr made, ok to final
ELE06-01862 Final5/25/20065/30/20065/30/2006 9:15:05 AMAPASS
clyde; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
ELE06-01862 Permanent Service5/30/20065/30/20065/30/2006 9:14:38 AMAPASS
clyde; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections made, p/s o/h rec ok
ELE06-00921 Final5/30/20065/30/20065/30/2006 8:31:49 AMAPART
Scheduled by a contractor via Hello! on 5/30/2006 at 6:09:52 AM. Contact: ###-####. all checked except adding generator for later, signed t/o card, will call ltr