FIR06-00104
| FIR-Aging Inspection | 5/30/2006 | 5/30/2006 | 6/1/2006 8:14:22 AM | | NR |
|
|
work in progress
|
FIR06-00374
| INSP-Final Inspection | 5/30/2006 | 5/30/2006 | 5/30/2006 9:12:18 PM | P | CANC |
|
|
No time for inspection today
|
BLD05-02957
| FIRE-Final Inspection | 5/30/2006 | 5/30/2006 | 5/30/2006 4:17:52 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung call first
|
BLD05-02722
| FIRE-Final Inspection | 5/30/2006 | 5/30/2006 | 5/30/2006 4:17:15 PM | P | FAIL |
|
|
Remove the exit sign to the rear office or change hardware and also provide approved hardware on all doors.
|
BLD06-00517
| FIRE-Conference | 5/30/2006 | 5/30/2006 | 5/30/2006 3:40:55 PM | A | CANC |
|
|
Fire life safety inspection not required.
|
BLD05-02489
| FIRE-Final Inspection | 5/26/2006 | 5/30/2006 | 5/30/2006 2:52:05 PM | A | FAIL |
|
|
Fire alarm permit needs to be finaled. When that is done then life safety can be signed off.
|
FIR06-00380
| INSP-Final Inspection | 5/30/2006 | 5/30/2006 | 5/30/2006 2:45:18 PM | P | FAIL |
|
|
Need ceiling tile installed
|
BLD05-01694
| FIRE-Final Inspection | 5/30/2006 | 5/30/2006 | 5/30/2006 2:44:20 PM | P | PASS |
|
|
Life safety finaled
|
FIR06-00146
| INSP-Final Inspection | 5/26/2006 | 5/30/2006 | 5/30/2006 2:43:39 PM | A | PASS |
|
|
permit finaled
|
FIR06-00026
| INSP-Final Inspection | 5/30/2006 | 5/30/2006 | 5/30/2006 12:29:36 PM | P | PASS |
|
|
Permit finaled
|
BLD06-00634
| FIRE-Final Inspection | 5/25/2006 | 5/30/2006 | 5/30/2006 11:29:14 AM | A | PASS |
|
|
Life safety finaled
|
FIR06-00196
| INSP-Final Inspection | 5/30/2006 | 5/30/2006 | 5/30/2006 11:28:53 AM | P | PASS |
|
|
Permit finaled
|
BLD06-01191
| FIRE-Final Inspection | 5/26/2006 | 5/30/2006 | 5/30/2006 11:03:40 AM | A | FAIL |
|
|
Provide lever hardware on the one door that was moved and install all ceiling tile.
|
BLD06-01189
| FIRE-Final Inspection | 5/26/2006 | 5/30/2006 | 5/30/2006 11:01:41 AM | A | PASS |
|
|
Life safety finaled
|
FIR06-00281
| INSP-Sprinkler Rough-in | 5/26/2006 | 5/30/2006 | 5/30/2006 9:58:58 AM | A | PASS |
|
|
Corrections as noted on the approved plans have been corrected. Sprinkler piping is ok to cover.
|
BLD06-00324
| FIRE-Final Inspection | 5/26/2006 | 5/30/2006 | 5/30/2006 9:20:15 AM | A | CANC |
|
|
greg 5th floor; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
FIR06-00288
| INSP-Final Inspection | 5/26/2006 | 5/30/2006 | 5/30/2006 9:15:33 AM | A | FAIL |
|
|
Pendant sprinklers overspaced. Small room rule can not be used. (This activity was added in error so we have changed the case status back to Issued.)
|
BLD06-00322
| FIRE-Final Inspection | 5/30/2006 | 5/30/2006 | 5/30/2006 9:05:55 AM | P | FAIL |
|
|
Final sprinkler permit and provide permanant emergency lighting and the additional exit signs in corridor.
|
FIR06-00286
| INSP-Final Inspection | 5/26/2006 | 5/30/2006 | 5/30/2006 9:04:43 AM | A | FAIL |
|
|
Sprinkler pendants are overspaced in the conference room. Small room rule can not be used.
|
BLD06-00320
| FIRE-Final Inspection | 5/26/2006 | 5/30/2006 | 5/30/2006 8:50:01 AM | A | FAIL |
|
|
provide one additional fire extinguisher and provide the additional exit signs inside/outside the exit lobby as shown on sheet el-106
|
FIR06-00192
| INSP-Final Inspection | 5/26/2006 | 5/30/2006 | 5/30/2006 8:18:32 AM | A | PASS |
|
|
permit finaled
|
FIR06-00247
| INSP-Final Inspection | 5/26/2006 | 5/30/2006 | 5/30/2006 12:00:00 AM | A | FAIL |
|
|
keith; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
Items need to be addressed prior to inspection:
1) Resubmittal required
2) Pull station at SE exit at 51"
3) duct detectors are not installed per manufacturer's installation requirements. Inspector will accept differential reading (inspector verifies) or third party measurements.
4) Ceiling mounted H/S are overspaced (internal)
5) Exterior H/S have Gentex WP covers, cutsheet required at resubmittal to verify no visual loss.
Tested the following:
Water flow: address 11
Tampers (5): address 12
PIV (1): address 13
|
FIR05-00708
| INSP-Sprinkler Rough-in/Hydro | 5/30/2006 | 5/30/2006 | 5/30/2006 12:00:00 AM | P | PASS |
|
|
OK to cover.
Scheduled by a contractor via Hello! on 5/30/2006 at 4:56:40 AM. Contact: ###-####.
|
BLD05-02758
| FIRE-Final Inspection | 5/26/2006 | 5/30/2006 | 5/30/2006 12:00:00 AM | P | FAIL |
|
|
Bill Davis; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
Fire extinguishers mounted at 51" should be 48" to lever.
2) Provide emergency lighting for Hall 104 and Hall at office 127
2) Doors to lease spaces 201 and 301 are mounted backwards
4) Final Fire Alarm Permit
|
FIR06-00130
| INSP-Final Inspection | 5/26/2006 | 5/30/2006 | 5/30/2006 12:00:00 AM | P | FAIL |
|
|
Troy, We would like to schedule for sometime in the afternoon. Please call us when you have a time. Jason, Mike, or Ken; Phone #: ###-#### Internet Inspection Request from: Jason Minnick
No inspection performed:
7 ea. duct detectors are not installed per manufacturer's installation requirements. Inspector will accept differential reading (inspector verifies) or third party measurements.
|
FIR06-00274
| INSP-Sprinkler Rough-in/Hydro | 5/30/2006 | 5/30/2006 | 5/30/2006 12:00:00 AM | P | FAIL |
|
|
Failed: 2 ECOH heads obstructed by exposed round duct. Stockroom floor coverage is lacking/obstructed by HVAC/Ducts
Contact: Steve - Cover; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
|
FIR06-00341
| INSP-Sprinkler Rough-in/Hydro | 5/30/2006 | 5/30/2006 | 5/30/2006 12:00:00 AM | P | PASS |
|
|
OK to cover.
Contact: Steve - Cover; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
|