Inspections for the day of: Tuesday, May 30, 2006.
Number of inspections: 27
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00104 FIR-Aging Inspection5/30/20065/30/20066/1/2006 8:14:22 AM NR
work in progress
FIR06-00374 INSP-Final Inspection5/30/20065/30/20065/30/2006 9:12:18 PMPCANC
No time for inspection today
BLD05-02957 FIRE-Final Inspection5/30/20065/30/20065/30/2006 4:17:52 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung call first
BLD05-02722 FIRE-Final Inspection5/30/20065/30/20065/30/2006 4:17:15 PMPFAIL
Remove the exit sign to the rear office or change hardware and also provide approved hardware on all doors.
BLD06-00517 FIRE-Conference5/30/20065/30/20065/30/2006 3:40:55 PMACANC
Fire life safety inspection not required.
BLD05-02489 FIRE-Final Inspection5/26/20065/30/20065/30/2006 2:52:05 PMAFAIL
Fire alarm permit needs to be finaled. When that is done then life safety can be signed off.
FIR06-00380 INSP-Final Inspection5/30/20065/30/20065/30/2006 2:45:18 PMPFAIL
Need ceiling tile installed
BLD05-01694 FIRE-Final Inspection5/30/20065/30/20065/30/2006 2:44:20 PMPPASS
Life safety finaled
FIR06-00146 INSP-Final Inspection5/26/20065/30/20065/30/2006 2:43:39 PMAPASS
permit finaled
FIR06-00026 INSP-Final Inspection5/30/20065/30/20065/30/2006 12:29:36 PMPPASS
Permit finaled
BLD06-00634 FIRE-Final Inspection5/25/20065/30/20065/30/2006 11:29:14 AMAPASS
Life safety finaled
FIR06-00196 INSP-Final Inspection5/30/20065/30/20065/30/2006 11:28:53 AMPPASS
Permit finaled
BLD06-01191 FIRE-Final Inspection5/26/20065/30/20065/30/2006 11:03:40 AMAFAIL
Provide lever hardware on the one door that was moved and install all ceiling tile.
BLD06-01189 FIRE-Final Inspection5/26/20065/30/20065/30/2006 11:01:41 AMAPASS
Life safety finaled
FIR06-00281 INSP-Sprinkler Rough-in5/26/20065/30/20065/30/2006 9:58:58 AMAPASS
Corrections as noted on the approved plans have been corrected. Sprinkler piping is ok to cover.
BLD06-00324 FIRE-Final Inspection5/26/20065/30/20065/30/2006 9:20:15 AMACANC
greg 5th floor; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
FIR06-00288 INSP-Final Inspection5/26/20065/30/20065/30/2006 9:15:33 AMAFAIL
Pendant sprinklers overspaced. Small room rule can not be used. (This activity was added in error so we have changed the case status back to Issued.)
BLD06-00322 FIRE-Final Inspection5/30/20065/30/20065/30/2006 9:05:55 AMPFAIL
Final sprinkler permit and provide permanant emergency lighting and the additional exit signs in corridor.
FIR06-00286 INSP-Final Inspection5/26/20065/30/20065/30/2006 9:04:43 AMAFAIL
Sprinkler pendants are overspaced in the conference room. Small room rule can not be used.
BLD06-00320 FIRE-Final Inspection5/26/20065/30/20065/30/2006 8:50:01 AMAFAIL
provide one additional fire extinguisher and provide the additional exit signs inside/outside the exit lobby as shown on sheet el-106
FIR06-00192 INSP-Final Inspection5/26/20065/30/20065/30/2006 8:18:32 AMAPASS
permit finaled
FIR06-00247 INSP-Final Inspection5/26/20065/30/20065/30/2006 12:00:00 AMAFAIL
keith; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles

Items need to be addressed prior to inspection:

1) Resubmittal required
2) Pull station at SE exit at 51"
3) duct detectors are not installed per manufacturer's installation requirements. Inspector will accept differential reading (inspector verifies) or third party measurements.
4) Ceiling mounted H/S are overspaced (internal)
5) Exterior H/S have Gentex WP covers, cutsheet required at resubmittal to verify no visual loss.

Tested the following:

Water flow: address 11
Tampers (5): address 12
PIV (1): address 13
FIR05-00708 INSP-Sprinkler Rough-in/Hydro5/30/20065/30/20065/30/2006 12:00:00 AMPPASS
OK to cover.

Scheduled by a contractor via Hello! on 5/30/2006 at 4:56:40 AM. Contact: ###-####.
BLD05-02758 FIRE-Final Inspection5/26/20065/30/20065/30/2006 12:00:00 AMPFAIL
Bill Davis; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt

Fire extinguishers mounted at 51" should be 48" to lever.

2) Provide emergency lighting for Hall 104 and Hall at office 127

2) Doors to lease spaces 201 and 301 are mounted backwards

4) Final Fire Alarm Permit
FIR06-00130 INSP-Final Inspection5/26/20065/30/20065/30/2006 12:00:00 AMPFAIL
Troy, We would like to schedule for sometime in the afternoon. Please call us when you have a time. Jason, Mike, or Ken; Phone #: ###-#### Internet Inspection Request from: Jason Minnick

No inspection performed:

7 ea. duct detectors are not installed per manufacturer's installation requirements. Inspector will accept differential reading (inspector verifies) or third party measurements.
FIR06-00274 INSP-Sprinkler Rough-in/Hydro5/30/20065/30/20065/30/2006 12:00:00 AMPFAIL
Failed: 2 ECOH heads obstructed by exposed round duct. Stockroom floor coverage is lacking/obstructed by HVAC/Ducts

Contact: Steve - Cover; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
FIR06-00341 INSP-Sprinkler Rough-in/Hydro5/30/20065/30/20065/30/2006 12:00:00 AMPPASS
OK to cover.

Contact: Steve - Cover; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley