Inspections for the day of: Wednesday, May 30, 2007.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00935 FIR-Aging Inspection5/30/20075/30/20076/7/2007 1:53:38 PM DEFR
FIR06-00006 INSP-Final Inspection5/29/20075/30/20075/31/2007 2:21:52 PMAPASS
Verified corrections, fire sprinkler permit finaled.
BLD06-02053 FIRE-Final Inspection5/29/20075/30/20075/30/2007 3:22:00 PMPFAIL
Provide approved door hardware at four locations, repair and retest emergency exit discharge lights on both the first and second floors.
FIR07-00258 INSP-Final Inspection5/30/20075/30/20075/30/2007 2:01:40 PMPPASS
Fire alarm permit finaled.
BLD06-00591 FIRE-Final Inspection5/29/20075/30/20075/30/2007 1:49:52 PMAPASS
Required corrections have been verified for completion, life safety inspection passed.
FIR07-00197 INSP-Final Inspection5/29/20075/30/20075/30/2007 12:00:43 PMAPART
Inspection for the core lobby area and the restroom fire sprinkler work passed.
FIR07-00391 INSP-Final Inspection5/29/20075/30/20075/30/2007 11:58:17 AMAPASS
Fire sprinkler modifications passed inspection, no permit documents on site.
FIR07-00258 INSP-Alarm Testing5/29/20075/30/20075/30/2007 11:53:56 AMAPASS
Fire alarm work tested satisfactory, one damper at the entry lobby south side adjusted while on site, also requested contractor designate inspection as a final when intended.
FIR07-00204 INSP-Sprinkler Rough-in5/29/20075/30/20075/30/2007 11:48:46 AMAPART
NW stair ceiling third floor fire sprinklers are approved for cover, also discussed flange hanger attatchments for the 4" main and trapeeze assemblies.