Inspections for the day of: Friday, May 30, 2008.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Johnson
TitlePLM-INSPECTOR
Phone #794-9476
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM08-01147 Plumbing Rough-in5/30/20085/30/20085/30/2008 4:15:15 PMPPASS
PLM07-03718 Water and/or Sewer5/30/20085/30/20085/30/2008 3:21:05 PMAPART
investigating complaint on water line
PLM08-00721 Final5/30/20085/30/20085/30/2008 2:51:23 PMPNR
Call Joe please. Phone #: ###-#### Internet Inspection Request from: joe paige not ready
PLM08-00722 Final5/30/20085/30/20085/30/2008 2:51:00 PMPNR
Call Joe please. Phone #: ###-#### Internet Inspection Request from: joe paige not ready
PLM08-00808 Final5/30/20085/30/20085/30/2008 2:12:51 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Todd Hill
PLM08-00369 PLM-Aging Inspection5/30/20085/30/20085/30/2008 1:24:35 PM PASS
project under construction
PLM08-00628 PLM-Aging Inspection5/30/20085/30/20085/30/2008 1:19:45 PM PASS
no request for final
PLM08-01275 Sprinkler (Final)5/29/20085/30/20085/30/2008 11:31:11 AMAFAIL
r.j. Phone #: ###-#### need to move ball valve with #1 test port to inlet side of double check and provide blow out tee on outlet side of double check. #2- need to move control valves and backflow device on to approved lot for building located at 128 peasley
PLM08-01274 Sprinkler (Final)5/29/20085/30/20085/30/2008 11:26:34 AMAFAIL
r.j. Phone #: ###-#### neeed to install double check as per manufacture instruction need to move ball valve with #1 test port to inlet side and provide blow out tee on outlet side of backflow device