Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01407 Final5/30/20085/30/20085/30/2008 4:15:54 PMPPASS
Ready for final inspection today. Please call tim if more information is needed. Phone #: ###-#### Internet Inspection Request from: Kathy Macdonald ground rods ok, ok to final
ELE08-01284 Final5/30/20085/30/20085/30/2008 2:58:14 PMPFAIL
Late in day if possible. thanks. Final on trailer used for snow cone shack. trailer will be in drive and open. Phone #: ###-#### Internet Inspection Request from: Randy Fletcher called contractor, left correction notice,NEC 314.28(C) shall install cover for outside box or light?, 314.21 shall repair surface around junction box, 406.4 receptacles shall be mounted such that they are rigidly mounted and after installation faceplates are flush with or project from finished surface, 110.3(B) listed equipment shall be installed and used in accordance with instructions in listing- panel for service, no esc listed
ESC08-00195 General Inspection5/30/20085/30/20085/30/2008 2:07:23 PMPPASS
looked ok
ESC08-00303 General Inspection5/30/20085/30/20085/30/2008 1:56:19 PMAPASS
looked ok
ESC07-01292 General Inspection5/30/20085/30/20085/30/2008 1:54:37 PMAPASS
looked ok
ELE08-01378 Permanent Service5/30/20085/30/20085/30/2008 1:23:29 PMPPASS
p/s o/h n ok
ELE08-01378 Electrical Rough-In5/29/20085/30/20085/30/2008 1:19:05 PMPPASS
dustin - late as possible please Phone #: ###-#### ric house only ok, u/g house to garage ok - will see garage at final
ELE08-00593 Final5/30/20085/30/20085/30/2008 12:30:21 PMPNH
sam Phone #: ###-#### called contractor, needs meter for house panel, but locked up, told to call when can get access, needs sticker on whole service, needs to label house panel meter
ELE08-01170 Electrical Rough-In5/29/20085/30/20085/30/2008 10:44:09 AMAPASS
bonding trac inspection any questions please call kevin @ ###-#### Phone #: ###-#### Internet Inspection Request from: Jari Rivers track bonding ok
ELE08-01331 Final5/29/20085/30/20085/30/2008 10:39:06 AMAPART
Donny Phone #: ###-#### main part electrical ok , left correction notice,reviewed with contractor and electrician. BCC no violations shall be retained, NEC 358.30 emt shall be strapped within 3' of termination, 330.30 mc shall be strapped within 12" of box, 408.4 circuit diectory shall be clear, concise, definitive, 110.26 shall provide work space about electrical equipment, 110.12(A) shall install covers on boxes, 725.3(B) abandoned class 2&3 cables shall be removed, 300.11 cable assemblies shall be securely fastened in place- not on grid or tiles, 230.70(B) shall label service disconnect, no esc permit
ELE08-01434 Electrical Rough-In5/29/20085/30/20085/30/2008 10:16:45 AMAPASS
trench inspection permission to cover Phone #: ###-#### Internet Inspection Request from: Andy Derrick u/g ok to cover
ELE08-01383 Electrical Rough-In5/29/20085/30/20085/30/2008 9:47:51 AMAPASS
brian Phone #: ###-#### u/g ok to cover, gazebo and planter ri ok
ELE08-01427 Temporary Service5/29/20085/30/20085/30/2008 9:03:17 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe t/s o/h n ok
ELE08-01344 Electrical Rough-In5/29/20085/30/20085/30/2008 8:43:28 AMAPASS
CONTACT: LEON SHEFFIELD - UNDERGROUND INSPECTION PLEASE Phone #: ###-#### Internet Inspection Request from: Deb Gooden u/g ok to cover, told contractor to tie esc permit to electrical if available
ELE08-01416 Temporary Service5/28/20085/30/20085/30/2008 8:19:53 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson t/s u/g n ok, no esc listed
ELE08-01417 Temporary Service5/28/20085/30/20085/30/2008 8:19:13 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson t/s u/g n ok, no esc listed