Inspections for the day of: Wednesday, May 30, 2012.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-00002 FIRE-Final Inspection5/29/20125/30/20125/30/2012 4:03:36 PMAFAIL
The required street width as approved by the fire dept. has not been met. Romeo Gervais has been notified and has requested information from the engineer prior to a sign off on this permit. All other items are ok.
BLD11-02685 FIRE-Final Inspection5/30/20125/30/20125/30/2012 4:01:53 PMPCANC
The required street width as approved by the fire dept. has not been met. Romeo Gervais has been notified and has requested information from the engineer prior to a sign off on this permit. All other items are ok.
BLD12-01204 FIRE-Final Inspection5/30/20125/30/20125/30/2012 3:36:07 PMPFAIL
Provide exit signs , as shown on the approved plans. The exit sign placement at the main exit is ok. Provide emergency lighting in the warehouse and office areas. Additional lighting is required at the north end of the warehouse. Provide single action, lever, hardware on all exterior exit doors as per the approved plans. Remove all dead bolts. The main exit door is ok to be keyed as long as the sticker "door to remain unlocked when buildign is occupied" is place at the exit. Provide singel action hardware on the interior doors at the pass through from the warehouse and the east office. Provide 2A, 10BC fire extinguishers with current inspection tags mounted 5' to 4" off of the finish floor. Provide two in the warehouse and one for the office area.
BLD12-00828 FIRE-Final Inspection5/30/20125/30/20125/30/2012 3:16:20 PMPPASS
life safety passed
BLD12-00827 FIRE-Conference5/30/20125/30/20125/30/2012 3:15:22 PMPDONE
Bill and I went over life safety requirements. One exit at the end of a short corridor, with exit sign/emergency light on the north side of the building, has been walled off and is now in an office. Also Bill is interested in possibly deleting exit signs. I deferred deleting signs and the wall changes to the plan reviewer for re-verification. We also discussed relocating signs to where they will be more visable. Door hardware is not yet complete nor is the south store front assembly.
FIR12-00250 INSP-Sprinkler Rough-in/Hydro5/30/20125/30/20125/30/2012 2:04:15 PMPPASS
Overhead hydro test passed. Rough-in passed. Sprinkler piping can be covered.
BLD12-00860 FIRE-Sprinkler Rough-in5/30/20125/30/20125/30/2012 2:03:39 PMPPASS
Sprinkler piping is ok to cover.
FIR12-00257 INSP-Final Inspection5/30/20125/30/20125/30/2012 1:23:46 PMPCANC
No access to project. Sam will reschedule.
FIR12-00256 INSP-Final Inspection5/30/20125/30/20125/30/2012 1:23:20 PMPCANC
No access to project. Sam will reschedule.