ELE18-01984
| Rough-In Permanent Service | 5/29/2018 | 5/30/2018 | 5/30/2018 2:45:36 PM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk
|
ELE18-02004
| Permanent Service | 5/30/2018 | 5/30/2018 | 5/30/2018 2:45:27 PM | P | PASS |
|
|
Casey Phone #: ###-#### 2nd meter being added to meter power used in garage seperate from house for business purposes. Garage is to have covered walls in future. Informed at time of final all horizontal wiring shall be protected from damage as per 110.27. Feeders and grounding done at time of inspection. p/s o/h rec ok
|
ELE18-02017
| Permanent Service | 5/30/2018 | 5/30/2018 | 5/30/2018 2:32:09 PM | P | PASS |
|
|
Mast damaged by tree limb and being replaced. Plumbing bond in place and ground rods going in at time of inspection. Will confirm labels, grounding, intersystem bond at final. p/s o/h rec ok
|
ELE18-01113
| Final | 5/30/2018 | 5/30/2018 | 5/30/2018 2:14:02 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Brad Girard Final ok
|
ELE18-02007
| Electrical Rough-In | 5/30/2018 | 5/30/2018 | 5/30/2018 1:55:32 PM | P | PASS |
|
|
Zac on site. Walls ri inspection. Phone #: ###-#### Inspection requested via web by Garrett Collins Main level bed and bath/ closets and basement bath rough in ok cover
|
ELE18-01724
| Electrical Rough-In | 5/30/2018 | 5/30/2018 | 5/30/2018 1:17:33 PM | P | PASS |
|
|
ug conduit Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Branch circuit underground to be done in future. Service entrance conduits under slab rough in ok cover
|
ELE18-01998
| Electrical Rough-In | 5/30/2018 | 5/30/2018 | 5/30/2018 12:43:51 PM | P | PASS |
|
|
Please call Tyler Reed (###-####) for specifics prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell Underground and stubs to footing and stem walls rough in ok cover
|
ELE17-04193
| Final | 5/29/2018 | 5/30/2018 | 5/30/2018 11:19:26 AM | A | FAIL |
|
|
Matt. Call prior to heading to the site. Phone #: ###-#### Inspection requested via web by Sean DeLacy 210.8(B)- All receptacle outlets located with in 6' of a sink shall have GFCI protection. Pop counter. 408.7- Unused openings shall be closed by approved means. High voltage panel needs breaker blanks. 426.28- Equipment shall be protected by an equipment protection device. EPD on heat tape circuit.
|
ELE18-01951
| Electrical Rough-In | 5/29/2018 | 5/30/2018 | 5/30/2018 10:46:20 AM | A | PASS |
|
|
ufer ug // go to CM construction gate // Mike Phone #: ###-#### Rough in ok cover
|
ELE17-01337
| Electrical Rough-In | 5/29/2018 | 5/30/2018 | 5/30/2018 10:17:01 AM | A | PASS |
|
|
We are requesting a final inspection for underground for tomorrow morning. Our contact is Rick @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Underground front pole lights and bases rough in ok cover
|
ELE18-01407
| Final | 5/29/2018 | 5/30/2018 | 5/30/2018 9:50:35 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mark M Final ok
|
ELE18-01968
| Rough-In Permanent Service | 5/25/2018 | 5/30/2018 | 5/30/2018 9:23:45 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk Rough in ok cover p/s u/g n ok
|