Inspections for the day of: Friday, May 31, 2002.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Schmer
TitleELE-CHIEF INSPECTOR
Phone #794-9423
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-01616 Final5/30/20025/31/20025/31/2002 12:00:00 AMAPASS
fn marv- added recp, installed switch rep & light in bath, changed & added fan boxes-###-####
ELE02-00231 Final5/30/20025/31/20025/31/2002 12:00:00 AMAPASS
###-#### DEREK
ELE02-01328 Electrical Rough-In5/30/20025/31/20025/31/2002 12:00:00 AMANR
r/i- mike cell ###-#### conference 5/31/2002 8:42:57 AM
ELE02-01218 Final5/30/20025/31/20025/31/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 05/30/2002 at 16:32:32. Contact: ###-####.
ELE02-01617 Final5/30/20025/31/20025/31/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 05/30/2002 at 18:08:08. Contact: ###-####. p/s o/h new - ok 5/31/2002 8:09:36 AM
ELE02-01492 Rough-In Permanent Service5/30/20025/31/20025/31/2002 12:00:00 AMANH
DON no access & no phone number posted 5/31/2002 9:01:56 AM
ELE02-01086 Electrical Rough-In5/30/20025/31/20025/31/2002 12:00:00 AMAPART
###-#### ERIC COVER UPSTAIRS 5/31/2002 9:36:50 AM
ELE02-01566 Electrical Rough-In5/30/20025/31/20025/31/2002 12:00:00 AMPPASS
tom- ###-#### r/i -call 1st before insp r/i on soffett's for lights - ok 5/31/2002 8:52:14 AM
ELE02-01630 Rough-In Permanent Service5/31/20025/31/20025/31/2002 12:00:00 AMPPASS
r/i & ser- ###-####- kathy p/s u/g new - ok 5/31/2002 1:35:36 PM
ELE02-01492 Final5/31/20025/31/20025/31/2002 12:00:00 AMPFAIL
DON ###-#### bnd ht & cold, ID neutral, Roof jack, grd rods 6' apart, grd. exiting meter need secured to meter, and grd bushing on meter side of nipple. STOP WORK POSTED for work and no permit on back of building. 5/31/2002 1:30:22 PM