Inspections for the day of: Tuesday, May 31, 2005.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01896 Temporary Service5/31/20055/31/20055/31/2005 4:22:48 PMPFAIL
please call prior to inspection///carl ###-#### met with owner and told him to use approved gec clamp to rod, and to prevent abrasion of gec thru panel, then to call when ready
ELE05-01888 Permanent Service5/27/20055/31/20055/31/2005 3:53:39 PMPFAIL
###-#### Lisa called and talked to contractor to provide abrasion protection for gnd electrode cond. left corr notice. 300.5
ELE05-01895 Permanent Service5/31/20055/31/20055/31/2005 2:44:47 PMPPASS
chuck ###-#### p/s u/g exst pedestal ok
ELE05-01897 Rough-In Permanent Service5/31/20055/31/20055/31/2005 12:36:52 PMPPASS
darren ###-#### called contr about np, gnd bush,box set-back. ric ok, p/s u/g n ok
ELE05-01872 Electrical Rough-In5/31/20055/31/20055/31/2005 8:59:24 AMAFAIL
Scheduled by a contractor via Hello! on 5/31/2005 at 6:39:39 AM. called contr, left message, left corr notice, do not cover tag. 110.12(C) there shall be no damaged parts, 300.4(D) cable shall be 1 1/4" from edge of framing member. BCC job id
ELE05-01097 Final5/26/20055/31/20055/31/2005 8:40:13 AMAPASS
Scheduled by a contractor via Hello! on 5/26/2005 at 1:49:24 PM. Contact: ###-####. corr made, ok to final