Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01982 Conference5/31/20065/31/20065/31/2006 3:50:40 PMPDONE
mike ###-#### called told clearence for motor controls required clearence as 110.26 states, all wiring in wet location shall meet code for location, and motors require disconnect as 430 states no exceptions to what NEC requires
ELE06-01873 Final5/30/20065/31/20065/31/2006 3:32:14 PMPPASS
home after 4:00; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok
ELE06-01704 Permanent Service5/31/20065/31/20065/31/2006 2:51:18 PMPNH
roger; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles notice called
ELE06-01927 Temporary Service5/31/20065/31/20065/31/2006 2:50:29 PMAPASS
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman t/s o/h new ok
ELE05-03029 Final5/31/20065/31/20065/31/2006 1:58:01 PMPPASS
ok
ELE06-01872 Electrical Rough-In5/31/20065/31/20065/31/2006 1:28:50 PMPPART
wall cover; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen
walls only ok
ELE06-01545 Final5/31/20065/31/20065/31/2006 12:22:38 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok
ELE06-01560 Conference5/30/20065/31/20065/31/2006 11:54:34 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung owner not doing work and u/g covered before inspection, and permit shall be for 1 rm and p/s
ELE06-01142 Final5/30/20065/31/20065/31/2006 10:41:25 AMAPASS
MORGAN; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok
ELE06-01836 Final5/30/20065/31/20065/31/2006 10:41:03 AMAFAIL
FINAL RE-INSPECTION PLEASE. NO GATE,NO FENCE, NO DOGS. THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall called needs to bond soffit vents, hose bib and bell box, called wayne will correct
ELE06-01969 Temporary Service5/30/20065/31/20065/31/2006 9:44:07 AMAPASS
Phone #: ###-#### Internet Inspection Request from: William Zerfas t/s o/h new ok
ELE04-02743 Electrical Rough-In5/30/20065/31/20065/31/2006 9:14:38 AMAFAIL

Phone #: ###-#### Internet Inspection Request from: Rita DeYoung corr. met owner 300.14, 300.4 nail plates and 11/4", 314.16 box fill steel cutins, bath rm shall be on own 20 amp circuit 210.52(D),11(C)(3),23(A)(2) 250.148 grd metal boxes, 404.9 grd switches, 110.3 use approved tool for crimp devices note if corr. not made or more violations created permit will be voided also shall complete trim out and final for basement and outside lights by driveway