ELE06-01982
| Conference | 5/31/2006 | 5/31/2006 | 5/31/2006 3:50:40 PM | P | DONE |
|
|
mike ###-#### called told clearence for motor controls required clearence as 110.26 states, all wiring in wet location shall meet code for location, and motors require disconnect as 430 states no exceptions to what NEC requires
|
ELE06-01873
| Final | 5/30/2006 | 5/31/2006 | 5/31/2006 3:32:14 PM | P | PASS |
|
|
home after 4:00; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok
|
ELE06-01704
| Permanent Service | 5/31/2006 | 5/31/2006 | 5/31/2006 2:51:18 PM | P | NH |
|
|
roger; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles notice called
|
ELE06-01927
| Temporary Service | 5/31/2006 | 5/31/2006 | 5/31/2006 2:50:29 PM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman t/s o/h new ok
|
ELE05-03029
| Final | 5/31/2006 | 5/31/2006 | 5/31/2006 1:58:01 PM | P | PASS |
|
|
ok
|
ELE06-01872
| Electrical Rough-In | 5/31/2006 | 5/31/2006 | 5/31/2006 1:28:50 PM | P | PART |
|
|
wall cover; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen walls only ok
|
ELE06-01545
| Final | 5/31/2006 | 5/31/2006 | 5/31/2006 12:22:38 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok
|
ELE06-01560
| Conference | 5/30/2006 | 5/31/2006 | 5/31/2006 11:54:34 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung owner not doing work and u/g covered before inspection, and permit shall be for 1 rm and p/s
|
ELE06-01142
| Final | 5/30/2006 | 5/31/2006 | 5/31/2006 10:41:25 AM | A | PASS |
|
|
MORGAN; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok
|
ELE06-01836
| Final | 5/30/2006 | 5/31/2006 | 5/31/2006 10:41:03 AM | A | FAIL |
|
|
FINAL RE-INSPECTION PLEASE. NO GATE,NO FENCE, NO DOGS. THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall called needs to bond soffit vents, hose bib and bell box, called wayne will correct
|
ELE06-01969
| Temporary Service | 5/30/2006 | 5/31/2006 | 5/31/2006 9:44:07 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: William Zerfas t/s o/h new ok
|
ELE04-02743
| Electrical Rough-In | 5/30/2006 | 5/31/2006 | 5/31/2006 9:14:38 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung corr. met owner 300.14, 300.4 nail plates and 11/4", 314.16 box fill steel cutins, bath rm shall be on own 20 amp circuit 210.52(D),11(C)(3),23(A)(2) 250.148 grd metal boxes, 404.9 grd switches, 110.3 use approved tool for crimp devices note if corr. not made or more violations created permit will be voided also shall complete trim out and final for basement and outside lights by driveway
|