Inspections for the day of: Wednesday, May 31, 2006.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04290 ELE-Aging Inspection5/31/20065/31/20066/2/2006 12:58:34 PM DONE
called contr, still not ready for final, open corr notice
ELE05-04669 ELE-Aging Inspection5/31/20065/31/20066/2/2006 9:36:17 AM DONE
see final
ELE06-01084 ELE-Aging Inspection5/31/20065/31/20066/1/2006 10:23:10 AM DONE
called, suc
ELE06-01972 Electrical Rough-In5/30/20065/31/20065/31/2006 4:12:29 PMPPASS
Please contact Dan Wilken, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters 2 walls only ok to cover
ELE06-00812 Final5/30/20065/31/20065/31/2006 3:54:00 PMPPASS
brian; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok to final
ELE06-01314 Electrical Rough-In5/31/20065/31/20065/31/2006 3:27:53 PMPPASS
todd Note; ceiling; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover ceiling only
ELE05-04010 Final5/31/20065/31/20065/31/2006 2:50:40 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung corrections made, ok to final
ELE06-01983 Temporary Service5/31/20065/31/20065/31/2006 2:17:55 PMPFAIL
###-#### called contr, left corr notice, nec 312.5 abrasion protection shall be provided for all conductors entering enclosures, 310.7 conductors used for direct burial shall be of a type identified for such use
ELE06-01984 Temporary Service5/31/20065/31/20065/31/2006 1:45:39 PMPFAIL
###-#### - joe called contr, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 310.7 conductors used for direct burial shall be of a type identified for such use
ELE06-01155 Rough-In Permanent Service5/31/20065/31/20065/31/2006 12:49:32 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla wrong house
ELE06-01153 Rough-In Permanent Service5/31/20065/31/20065/31/2006 12:49:01 PMPPASS
called contr, they said this is address and permit, ric ok, p/s u/g n ok
ELE06-01966 Temporary Service5/30/20065/31/20065/31/2006 12:00:16 PMANR
Verna; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called no address
ELE06-01313 Electrical Rough-In5/31/20065/31/20065/31/2006 10:41:31 AMPFAIL
Scheduled by a contractor via Hello! on 5/31/2006 at 7:30:43 AM. Contact: ###-####. called contr, left corr notice,nec 352.30)A) rnc shall be strapped within 3' of box, 110.3(B) listed or labelled equip shall be installed with instructions included, 300.4(A)&(D) edge of holes and raceway shall be 1 1/4" from edge of framing member, BCC all make-up shall be done, low voltage shall be installed
ELE06-01968 Temporary Service5/30/20065/31/20065/31/2006 10:25:59 AMANR
Verna; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called no address
ELE05-04010 Final5/30/20065/31/20065/31/2006 9:31:53 AMAFAIL
call first ; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung called contr, left corr notice, nec 352.30(A) rnc shall be supported within 3' of panel,250.64(B) gec shall be secured to surface, 408.4 circuit directory shall be provided,110.3(B) disposal shall be wired, reverse polarity on recpt on island shall be corrected, 422.31(B) furnace disconnect shall be supplied
ELE06-01971 Temporary Service5/30/20065/31/20065/31/2006 8:36:08 AMAFAIL
###-#### called contr, left message, left corr notice, nec 312.5 all conductors entering enclosure shall have abrasion protection, 250.8 bonding jumper shall be connected, 110.12(C) there shall be no broken parts (50A recpt), fee due
ELE06-01960 Temporary Service5/30/20065/31/20065/31/2006 8:09:06 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung called contr, left survey, t/s u/g n ok