ELE05-04290
| ELE-Aging Inspection | 5/31/2006 | 5/31/2006 | 6/2/2006 12:58:34 PM | | DONE |
|
|
called contr, still not ready for final, open corr notice
|
ELE05-04669
| ELE-Aging Inspection | 5/31/2006 | 5/31/2006 | 6/2/2006 9:36:17 AM | | DONE |
|
|
see final
|
ELE06-01084
| ELE-Aging Inspection | 5/31/2006 | 5/31/2006 | 6/1/2006 10:23:10 AM | | DONE |
|
|
called, suc
|
ELE06-01972
| Electrical Rough-In | 5/30/2006 | 5/31/2006 | 5/31/2006 4:12:29 PM | P | PASS |
|
|
Please contact Dan Wilken, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters 2 walls only ok to cover
|
ELE06-00812
| Final | 5/30/2006 | 5/31/2006 | 5/31/2006 3:54:00 PM | P | PASS |
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok to final
|
ELE06-01314
| Electrical Rough-In | 5/31/2006 | 5/31/2006 | 5/31/2006 3:27:53 PM | P | PASS |
|
|
todd Note; ceiling; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover ceiling only
|
ELE05-04010
| Final | 5/31/2006 | 5/31/2006 | 5/31/2006 2:50:40 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung corrections made, ok to final
|
ELE06-01983
| Temporary Service | 5/31/2006 | 5/31/2006 | 5/31/2006 2:17:55 PM | P | FAIL |
|
|
###-#### called contr, left corr notice, nec 312.5 abrasion protection shall be provided for all conductors entering enclosures, 310.7 conductors used for direct burial shall be of a type identified for such use
|
ELE06-01984
| Temporary Service | 5/31/2006 | 5/31/2006 | 5/31/2006 1:45:39 PM | P | FAIL |
|
|
###-#### - joe called contr, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 310.7 conductors used for direct burial shall be of a type identified for such use
|
ELE06-01155
| Rough-In Permanent Service | 5/31/2006 | 5/31/2006 | 5/31/2006 12:49:32 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla wrong house
|
ELE06-01153
| Rough-In Permanent Service | 5/31/2006 | 5/31/2006 | 5/31/2006 12:49:01 PM | P | PASS |
|
|
called contr, they said this is address and permit, ric ok, p/s u/g n ok
|
ELE06-01966
| Temporary Service | 5/30/2006 | 5/31/2006 | 5/31/2006 12:00:16 PM | A | NR |
|
|
Verna; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called no address
|
ELE06-01313
| Electrical Rough-In | 5/31/2006 | 5/31/2006 | 5/31/2006 10:41:31 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 5/31/2006 at 7:30:43 AM. Contact: ###-####. called contr, left corr notice,nec 352.30)A) rnc shall be strapped within 3' of box, 110.3(B) listed or labelled equip shall be installed with instructions included, 300.4(A)&(D) edge of holes and raceway shall be 1 1/4" from edge of framing member, BCC all make-up shall be done, low voltage shall be installed
|
ELE06-01968
| Temporary Service | 5/30/2006 | 5/31/2006 | 5/31/2006 10:25:59 AM | A | NR |
|
|
Verna; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called no address
|
ELE05-04010
| Final | 5/30/2006 | 5/31/2006 | 5/31/2006 9:31:53 AM | A | FAIL |
|
|
call first ; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung called contr, left corr notice, nec 352.30(A) rnc shall be supported within 3' of panel,250.64(B) gec shall be secured to surface, 408.4 circuit directory shall be provided,110.3(B) disposal shall be wired, reverse polarity on recpt on island shall be corrected, 422.31(B) furnace disconnect shall be supplied
|
ELE06-01971
| Temporary Service | 5/30/2006 | 5/31/2006 | 5/31/2006 8:36:08 AM | A | FAIL |
|
|
###-#### called contr, left message, left corr notice, nec 312.5 all conductors entering enclosure shall have abrasion protection, 250.8 bonding jumper shall be connected, 110.12(C) there shall be no broken parts (50A recpt), fee due
|
ELE06-01960
| Temporary Service | 5/30/2006 | 5/31/2006 | 5/31/2006 8:09:06 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung called contr, left survey, t/s u/g n ok
|