Inspections for the day of: Thursday, May 31, 2007.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-01876 FIRE-Final Inspection5/31/20075/31/20076/1/2007 1:51:43 PMPPASS
Fire life safety finaled.
FIR06-00940 FIR-Aging Inspection5/31/20075/31/20076/1/2007 8:24:47 AM DEFR
Work in progress, building under construction.
BLD06-01392 FIRE-Final Inspection5/30/20075/31/20075/31/2007 3:13:14 PMAPASS
Fire life safety inspection passed, contractor to install one missing exit sign as indicated on approved plans, to be verified at next visit for the adjacent remodel final.
FIR06-00546 INSP-Final Inspection5/30/20075/31/20075/31/2007 3:11:22 PMAPASS
Fire sprinkler permit finaled, noted project modification to not complete the chest room as indicated on plans, upright protection is provided for the interm.
BLD06-00443 FIRE-Final Inspection5/31/20075/31/20075/31/2007 2:24:25 PMPPASS
Fire life safety finaled.
BLD06-02053 FIRE-Final Inspection5/31/20075/31/20075/31/2007 2:20:50 PMPPASS
Corrections are complete, fire life safety inspection passed.
FIR06-00007 INSP-Alarm Testing5/29/20075/31/20075/31/2007 2:05:11 PMAPART
Walk through testing of a/v notification at the 1st , 2nd and basement floor levels only completed today, noted one horn to be replaced in the basement, some areas on the first and second floors appear to be overspaced or obstructed as noted, as-built plans need to accurately reflect locations of all devices, the 1st floor pyro room may need an additional horn, clean room areas on the 1st floor remain to be verified for a/v testing due to access issues, audibility and synchronization throughout the remainder of the project are acceptable.
FIR07-00034 INSP-Sprinkler Rough-in/Hydro5/29/20075/31/20075/31/2007 11:27:10 AMAPART
Forward flow testing for the BFP and the class one standpipe roof connection completed acceptable.
BLD04-00945 FIRE-Final Inspection5/30/20075/31/20075/31/2007 10:55:20 AMAPASS
Final fire life safety inspection passed, noted the provided PFE's to be installed in the units prior to occupancy as required.