ELE07-01946
| Electrical Rough-In | 5/30/2007 | 5/31/2007 | 5/31/2007 4:04:45 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham ri ok, basement area only.
|
ELE07-01376
| Electrical Rough-In | 5/31/2007 | 5/31/2007 | 5/31/2007 3:49:36 PM | P | NH |
|
|
tom - trench; Phone #: ###-#### Internet Inspection Request from: Victoria no access they are paving the roads
|
ELE07-00420
| Final | 5/31/2007 | 5/31/2007 | 5/31/2007 3:13:13 PM | P | PASS |
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt
|
ELE07-01818
| Final | 5/31/2007 | 5/31/2007 | 5/31/2007 2:18:41 PM | P | PASS |
|
|
Please inspect overhead service lateral extension. if you have any questions please call Bryan @ ###-####. Thank you Phone #: ###-#### Internet Inspection Request from: todd hall this final is only for the raising of the mast, not for the garage addition
|
ELE07-01818
| Permanent Service | 5/31/2007 | 5/31/2007 | 5/31/2007 2:10:44 PM | P | PASS |
|
|
Please inspect overhead service lateral extension. if you have any questions please call Bryan @ ###-####. Thank you Phone #: ###-#### Internet Inspection Request from: todd hall p/s o/h reconnect ok, gounding has also been updated
|
ELE07-01192
| Final | 5/31/2007 | 5/31/2007 | 5/31/2007 1:53:06 PM | P | FAIL |
|
|
per Jim S. request 410.8 master bedroom 3 units, east unit is ok
|
ELE07-01551
| Electrical Rough-In | 5/31/2007 | 5/31/2007 | 5/31/2007 12:57:20 PM | P | PASS |
|
|
joe - 2nd floor corridor, west side; Phone #: ###-#### Internet Inspection Request from: Victoria Beall as noted on print ok for cover
|
ELE07-01931
| Final | 5/30/2007 | 5/31/2007 | 5/31/2007 12:21:19 PM | A | FAIL |
|
|
any questions please call Skip Kubik Phone #: ###-#### x0000 Internet Inspection Request from: Sandee Johnson 1. needs to tag well casing 2. provide info for correct fault current rating 3. label or listing info for unit as a whole
|
ELE07-00895
| Final | 5/31/2007 | 5/31/2007 | 5/31/2007 12:19:30 PM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/31/2007 at 5:21:34 AM. Contact: ###-####. final ok
|
ELE07-01861
| Permanent Service | 5/31/2007 | 5/31/2007 | 5/31/2007 12:19:10 PM | A | FAIL |
|
|
Please do as early as possible. Thanks, Richard Jones Phone #: ###-#### Internet Inspection Request from: Richard Jones 1. 314.41 Covers for the J-Boxes shall be of the same type material as the boxes themselves. 2. 344.30 Mast shall be secured within three feet of the top 3. 250.52A1 ground the water pipe within 5' of entrance to the building. 4. 250.53A ground rod shall be in full contact with the earth 5. 240.24D overcurrent devices shall not be located in a closet 6. 314.17B all cables entering into boxes shall be secured to the boxes B.C.C. "No violation shall be retained" KO seals and clamps shall be instaled on the boxes where theyare not being used.
|
ELE07-00896
| Final | 5/31/2007 | 5/31/2007 | 5/31/2007 11:17:15 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/31/2007 at 5:20:23 AM. Contact: ###-####. final ok
|
ELE06-03412
| Final | 5/30/2007 | 5/31/2007 | 5/31/2007 9:44:41 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham 410.8 master bedroom and upstairs bedrooms
|
ELE07-01953
| Electrical Rough-In | 5/30/2007 | 5/31/2007 | 5/31/2007 8:57:06 AM | A | PASS |
|
|
mark - call 30 min prior; Phone #: ###-#### Internet Inspection Request from: Victoria Beall floor wiring ok
|
ELE07-01776
| Rough-In Permanent Service | 5/30/2007 | 5/31/2007 | 5/31/2007 8:31:22 AM | A | PASS |
|
|
Joe Phone #: ###-#### Internet Inspection Request from: Joseph Zumwal ri ok p/s u/g new ok
|