Inspections for the day of: Thursday, May 31, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorWilliam E Thomas
TitleELE-INSPECTOR
Phone #794-9492
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01946 Electrical Rough-In5/30/20075/31/20075/31/2007 4:04:45 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham
ri ok, basement area only.
ELE07-01376 Electrical Rough-In5/31/20075/31/20075/31/2007 3:49:36 PMPNH
tom - trench; Phone #: ###-#### Internet Inspection Request from: Victoria
no access they are paving the roads
ELE07-00420 Final5/31/20075/31/20075/31/2007 3:13:13 PMPPASS
Mike; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt
ELE07-01818 Final5/31/20075/31/20075/31/2007 2:18:41 PMPPASS
Please inspect overhead service lateral extension. if you have any questions please call Bryan @ ###-####. Thank you Phone #: ###-#### Internet Inspection Request from: todd hall
this final is only for the raising of the mast, not for the garage addition
ELE07-01818 Permanent Service5/31/20075/31/20075/31/2007 2:10:44 PMPPASS
Please inspect overhead service lateral extension. if you have any questions please call Bryan @ ###-####. Thank you Phone #: ###-#### Internet Inspection Request from: todd hall
p/s o/h reconnect ok, gounding has also been updated
ELE07-01192 Final5/31/20075/31/20075/31/2007 1:53:06 PMPFAIL
per Jim S. request
410.8 master bedroom 3 units, east unit is ok
ELE07-01551 Electrical Rough-In5/31/20075/31/20075/31/2007 12:57:20 PMPPASS
joe - 2nd floor corridor, west side; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
as noted on print ok for cover
ELE07-01931 Final5/30/20075/31/20075/31/2007 12:21:19 PMAFAIL
any questions please call Skip Kubik Phone #: ###-#### x0000 Internet Inspection Request from: Sandee Johnson
1. needs to tag well casing
2. provide info for correct fault current rating
3. label or listing info for unit as a whole
ELE07-00895 Final5/31/20075/31/20075/31/2007 12:19:30 PMAPASS
Scheduled by a contractor via Hello! on 5/31/2007 at 5:21:34 AM. Contact: ###-####.
final ok
ELE07-01861 Permanent Service5/31/20075/31/20075/31/2007 12:19:10 PMAFAIL
Please do as early as possible. Thanks, Richard Jones Phone #: ###-#### Internet Inspection Request from: Richard Jones
1. 314.41 Covers for the J-Boxes shall be of the same type material as the boxes themselves.
2. 344.30 Mast shall be secured within three feet of the top
3. 250.52A1 ground the water pipe within 5' of entrance to the building.
4. 250.53A ground rod shall be in full contact with the earth
5. 240.24D overcurrent devices shall not be located in a closet
6. 314.17B all cables entering into boxes shall be secured to the boxes
B.C.C. "No violation shall be retained"
KO seals and clamps shall be instaled on the boxes where theyare not being used.
ELE07-00896 Final5/31/20075/31/20075/31/2007 11:17:15 AMAPASS
Scheduled by a contractor via Hello! on 5/31/2007 at 5:20:23 AM. Contact: ###-####.
final ok
ELE06-03412 Final5/30/20075/31/20075/31/2007 9:44:41 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham
410.8 master bedroom and upstairs bedrooms
ELE07-01953 Electrical Rough-In5/30/20075/31/20075/31/2007 8:57:06 AMAPASS
mark - call 30 min prior; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
floor wiring ok
ELE07-01776 Rough-In Permanent Service5/30/20075/31/20075/31/2007 8:31:22 AMAPASS
Joe Phone #: ###-#### Internet Inspection Request from: Joseph Zumwal
ri ok
p/s u/g new ok