BLD11-01062
| FIRE-Final Inspection | 5/31/2011 | 5/31/2011 | 6/1/2011 1:58:29 PM | P | PART |
|
|
C/N items completed with the exception of hardware issues at the restroom access corridor. Inspection done 5/31.
|
BLD11-00712
| FIRE-Final Inspection | 5/31/2011 | 5/31/2011 | 5/31/2011 4:00:12 PM | P | PASS |
|
|
Fire life safety completed satisfactory, inspection passed.
|
BLD11-00711
| FIRE-Final Inspection | 5/31/2011 | 5/31/2011 | 5/31/2011 3:59:07 PM | P | PASS |
|
|
Fire life safety finaled.
|
FIR11-00237
| INSP-Final Inspection | 5/31/2011 | 5/31/2011 | 5/31/2011 3:58:20 PM | P | PASS |
|
|
Fire alarm work passed inspection. Contractor to post updated map at the panel as agreed. Permit finaled.
|
FIR11-00198
| INSP-Final Inspection | 5/31/2011 | 5/31/2011 | 5/31/2011 3:56:49 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD11-00774
| FIRE-Final Inspection | 5/27/2011 | 5/31/2011 | 5/31/2011 3:55:40 PM | P | FAIL |
|
|
Need to post fire extinguisher with a current certification tag, provide approved hardware at the main entry/exit and back exit doors.
|
BLD11-00777
| FIRE-Final Inspection | 5/31/2011 | 5/31/2011 | 5/31/2011 3:52:16 PM | P | PASS |
|
|
Fire life safety inspection passed.
|
FIR11-00223
| INSP-Final Inspection | 5/31/2011 | 5/31/2011 | 5/31/2011 3:51:06 PM | P | PASS |
|
|
Fire sprinkler permit final approved.
|
FIR11-00158
| INSP-Final Inspection | 5/31/2011 | 5/31/2011 | 5/31/2011 3:50:22 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD11-00487
| FIRE-Final Inspection | 5/31/2011 | 5/31/2011 | 5/31/2011 3:49:50 PM | P | PASS |
|
|
Vanilla life safety passed.
|
BLD11-00488
| FIRE-Final Inspection | 5/31/2011 | 5/31/2011 | 5/31/2011 3:47:33 PM | P | PASS |
|
|
Vanilla life safety passed.
|
BLD11-00270
| FIRE-Final Inspection | 5/27/2011 | 5/31/2011 | 5/31/2011 1:21:55 PM | A | PART |
|
|
Fire life safety inspection passed after two EM lights repaired while on site. Final approval pending project related fire alarm permit final as noted.
|
FIR11-00064
| INSP-Final Inspection | 5/31/2011 | 5/31/2011 | 5/31/2011 1:18:31 PM | P | FAIL |
|
|
Zones, points and descriptors at offsite monitoring do not accurately correlate with signals transmitted- example; zone 36 point 11 duct detector supervisory reported as zone 11 manual pull station trouble.
|
FIR11-00202
| INSP-Sprinkler Rough-in | 5/31/2011 | 5/31/2011 | 5/31/2011 11:24:43 AM | P | PART |
|
|
Cold cavity protection verified. Overhead fire sprinkler installation approved for cover.
|
BLD11-00777
| FIRE-Conference | 5/31/2011 | 5/31/2011 | 5/31/2011 10:36:47 AM | A | DONE |
|
|
Discussion with contractor regarding items for final including repair two exit sign/EM lights, post max. occupant load sign, post PFE with current tag, add one exit sign per plan at restroom hall, test EM lights at grid ceilings, provide verification fire sprinkler system is current with an annual inspection.
|
BLD11-00889
| FIRE-Final Inspection | 5/27/2011 | 5/31/2011 | 5/31/2011 10:34:38 AM | A | PASS |
|
|
Fire life safety final okay pending max. occupant load sign is posted and a cap at the unused gas service line is installed as discussed.
|
FIR11-00223
| INSP-Final Inspection | 5/27/2011 | 5/31/2011 | 5/31/2011 10:29:54 AM | A | PART |
|
|
Fire sprinkler permit work okay for final pending verification existing system is current with an annual inspection.
|
FIR11-00223
| INSP-Sprinkler Rough-in | 5/27/2011 | 5/31/2011 | 5/31/2011 10:26:34 AM | A | PART |
|
|
OH rough-in passed.
|