Inspections for the day of: Thursday, May 31, 2012.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00210 INSP-Sprinkler Rough-in/Hydro5/31/20125/31/20126/1/2012 5:07:36 PMPPART
Overhead hydrostatic testing complete. Installation above the drop ceilings in the office area approved for cover.
BLD12-00294 FIRE-Final Inspection5/30/20125/31/20126/1/2012 5:06:08 PMACANC
Overbooked
FIR10-00213 FIR-Aging Inspection5/31/20125/31/20126/1/2012 6:50:15 AM DONE
BLD12-00635 FIRE-Final Inspection5/31/20125/31/20126/1/2012 6:48:22 AMPPASS
Fire life safety finaled.
FIR12-00215 INSP-Alarm Testing5/29/20125/31/20126/1/2012 6:47:07 AMPPASS
Fire alarm testing passed.
FIR12-00212 INSP-Alarm Testing5/29/20125/31/20126/1/2012 6:46:42 AMPPASS
Fire alarm testing passed.
FIR12-00213 INSP-Alarm Testing5/29/20125/31/20126/1/2012 6:46:12 AMPPASS
Fire alarm testing passed.
FIR12-00214 INSP-Alarm Testing5/29/20125/31/20126/1/2012 6:45:40 AMPPASS
Fire alarm testing passed.
BLD12-00669 FIRE-Final Inspection5/30/20125/31/20125/31/2012 1:58:35 PMAFAIL
Door hardware installed at five locations including the second level exit, main level restroom and three exit doors at the sanctuary do not meet the approved plan set hardware schedule. Also need to post the two required fire extinguishers per plan.
BLD11-02685 FIRE-Final Inspection5/30/20125/31/20125/31/2012 1:51:42 PMAPASS
Life safety finaled.
BLD12-00002 FIRE-Final Inspection5/30/20125/31/20125/31/2012 1:50:31 PMAPART
Final pending installation of two "no parking" signs. T.O. approval okayed per R. Gervais.
FIR12-00234 INSP-Final Inspection5/30/20125/31/20125/31/2012 1:45:09 PMAPASS
Fire alarm work passed inspection. Permit finaled.
BLD12-01295 FIRE-Final Inspection5/30/20125/31/20125/31/2012 1:34:19 PMAPASS
Life safety inspection completed acceptable.
BLD12-01313 FIRE-Final Inspection5/30/20125/31/20125/31/2012 1:33:17 PMAPASS
Life safety inspection passed.