Inspections for the day of: Friday, May 31, 2013.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00096 FIR-Aging Inspection5/31/20135/31/20136/4/2013 11:56:59 AM NR
I spoke to Curtis at SimplexGrinnell and he is going to follow up with Charlie and Steve on the job status.
FIR13-00163 INSP-Sprinkler Rough-in5/31/20135/31/20135/31/2013 4:01:53 PMPPASS
See the city approved plans for locations above hardlids where sprinkler piping can be covered.
BLD13-01311 FIRE-Final Inspection5/31/20135/31/20135/31/2013 1:32:56 PMPPASS
life safety passed
BLD13-01044 FIRE-Final Inspection5/31/20135/31/20135/31/2013 1:14:26 PMPPASS
life safety passed
FIR13-00132 INSP-Conference5/31/20135/31/20135/31/2013 11:41:14 AMPDONE
I let Jason know that the manual pull stations for the emergency alert system do not meet code since they are red in color. The code section is: NFPA 72 17.14.1.2 Manual pull stations for initiating other than fire alarm shall be permitted if the devices are differentiated from the manual fire alarm boxes by a color other than red and labeling.
BLD13-01311 FIRE-Final Inspection5/29/20135/31/20135/31/2013 11:16:49 AMAFAIL
Provide approved single action hardware for the main exit and provide service tag for the fire extinguisher.
FIR13-00081 INSP-Alarm Testing5/30/20135/31/20135/31/2013 10:47:02 AMADONE
Todays inspection was for the second floor. We verified spacing on all audio/visuals. Found several tht needed adjustment. Also five horns need to be changed to horn/strobes due to ceiling obstructions. Testing of the duct smoke detectors for hvac shutdown passed. It appears the fire/smoke dampers are wired backwards and access may be limited on some which will need to be addressed prior to the next inspection.
BLD13-01347 FIRE-Final Inspection5/30/20135/31/20135/31/2013 10:35:33 AMAPASS
life safety passed
BLD13-01337 FIRE-Final Inspection5/30/20135/31/20135/31/2013 8:57:48 AMAPASS
life safety passed