FIR15-00822
| INSP-Final Inspection | 5/27/2016 | 5/31/2016 | 5/31/2016 1:54:10 PM | A | FAIL |
|
|
Forward flow test passed with a temporary outlet to the exterior but it needs to be permanent as per discussion. Pressure at riser indicated 56psi. Plans and calculations submitted require a minimum of 75psi at base of riser.
|
FIR15-00909
| INSP-Sprinkler Rough-in | 5/27/2016 | 5/31/2016 | 5/31/2016 9:05:14 AM | A | PASS |
|
|
Remaining underground supply piping is ok to cover.
|
BLD16-00907
| FIRE-Final Inspection | 5/27/2016 | 5/31/2016 | 5/31/2016 8:28:42 AM | A | PASS |
|
|
Life safety passed. Suite number was being installed.
|