Inspections for the day of: Tuesday, May 31, 2016.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00822 INSP-Final Inspection5/27/20165/31/20165/31/2016 1:54:10 PMAFAIL
Forward flow test passed with a temporary outlet to the exterior but it needs to be permanent as per discussion. Pressure at riser indicated 56psi. Plans and calculations submitted require a minimum of 75psi at base of riser.
FIR15-00909 INSP-Sprinkler Rough-in5/27/20165/31/20165/31/2016 9:05:14 AMAPASS
Remaining underground supply piping is ok to cover.
BLD16-00907 FIRE-Final Inspection5/27/20165/31/20165/31/2016 8:28:42 AMAPASS
Life safety passed. Suite number was being installed.