Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00017 INSP-Sprinkler Rough-in5/31/20165/31/20165/31/2016 1:02:03 PMAPART
Tenting Inspection complete for overhead fire sprinkler piping in the 3rd level attic spaces as well as 4th level fire sprinkler piping, area's inspected approved for cover with exception to the breeze-ways, the piping crossing the breeze-way an all floors cannot be covered until an approved method is installed to keep this section of piping from freezing
BLD15-01930 FIRE-Final Inspection5/31/20165/31/20165/31/2016 11:10:00 AMPPASS
No fire sprinklers, smoke detectors are stand alone detectors, final life fire safety inspection passed/complete.
FIR15-00747 INSP-Final Inspection5/31/20165/31/20165/31/2016 10:31:00 AMAPART
Tested/Inspected duct detectors/HVAC unit shutdown, second level clean mech room as well as second level dirty mech room, all devices tested today operated correctly and provided unti shutdown for HVAC units.
FIR16-00287 INSP-Final Inspection5/27/20165/31/20165/31/2016 12:00:00 AMPCANC