Inspections for the day of: Wednesday, May 31, 2017.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00120 INSP-Supply line flush5/31/20175/31/20175/31/2017 2:11:17 PMPPASS
Under ground supply line flush passed
BLD17-00177 FIRE-Final Inspection5/31/20175/31/20175/31/2017 1:43:33 PMPPASS
Life safety passed. Non-sprinklered building and construction did not appear to effect the existing fire alarm system
FIR16-00664 INSP-Final Inspection5/31/20175/31/20175/31/2017 1:37:41 PMPCANC
Selonoid has not been installed yet.

Call Anthony when heading out. Thanks. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD17-01539 FIRE-Final Inspection5/30/20175/31/20175/31/2017 10:31:09 AMAPASS
life safety passed
FIR17-00080 INSP-Sprinkler Rough-in/Hydro5/30/20175/31/20175/31/2017 10:13:07 AMAPASS
The underground and system #2 hydro tests passed
FIR17-00143 INSP-Final Inspection5/30/20175/31/20175/31/2017 10:01:22 AMAFAIL
Need actual full size drawings, notes and data sheets, need a clear panel, per approved drawings alarm, trouble and supervisory signals report off site. Per the tech only alarms report off site.
FIR17-00097 INSP-Final Inspection5/30/20175/31/20175/31/2017 9:58:15 AMACANC
Fire alarm system not ready so no testing was performed. I let mike know we will need a forward flush test performed.
FIR16-00557 INSP-Final Inspection5/30/20175/31/20175/31/2017 9:09:47 AMAFAIL
All items appear ok except the fan in the Truck Bay is an obstruction and the forward flow test failed.
FIR16-00392 INSP-Final Inspection5/30/20175/31/20175/31/2017 9:08:56 AMAFAIL
All items tested ok except that the fan in the Truck Bay will need to be shut down upon flow of water. Resubmittals or as-builts will be required at the plan reviewers request.