Inspections for the day of: Thursday, May 31, 2018.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02029 Electrical Rough-In5/30/20185/31/20185/31/2018 2:56:12 PMPFAIL
Install floor box and receptacle in new wall in Macy’s department store Phone #: ###-#### Inspection requested via web by Steve Craig
No Building permit found, asked for building permit and was informed one does not exist. Not able to inspect until building permit pulled. As per Mike Jordan instructions created MIS and posted stop work order.
ELE18-01898 Permanent Service5/31/20185/31/20185/31/2018 2:25:54 PMPPASS
Change out panel in kitchen area Phone #: ###-#### Inspection requested via web by Kendra Lanham
Work included repacement of interior bussing of panel that had been damaged. All circuits being used are labelled those not labelled are off. Rough in ok.
ELE18-01898 Final5/31/20185/31/20185/31/2018 2:25:37 PMPPASS
Change out panel in kitchen area Phone #: ###-#### Inspection requested via web by Kendra Lanham Final ok
ELE18-00727 Electrical Rough-In5/31/20185/31/20185/31/2018 2:03:23 PMPPASS
Phone #: ###-#### Inspection requested via web by Tom Jenkins
Out front soffit ceiling rough in ok cover
MIS18-00206 ELE-Conference5/31/20185/31/20185/31/2018 1:14:19 PMPFAIL
per Chad Schendiman-Ele & Plm work being done w/o permits-he said to note tht the home is vacant and the key is above the front door
Posted stop work order-
family room wiring around beam, added cut in cans in family room ceiling, panel has a neutral not terminated correctly, family room receptacles, wiring hanging by stairs, upstairs new walls in bed and bath with wiring.
Double fee accessed for work with out permit.
ELE18-00915 Final5/30/20185/31/20185/31/2018 12:08:42 PMAFAIL
garage code 4024 Phone #: ###-#### Inspection requested via web by Darryn Coburn
110.3- Hood not working.
314.17(C)- Where boxes moved for tile NM sheath shall enter box a minimum of 1/4".
ELE18-00916 Final5/30/20185/31/20185/31/2018 12:07:21 PMAFAIL
garage code 4124 Phone #: ###-#### Inspection requested via web by Darryn Coburn
BCC 04-05-24(D)- Inspector shall have access to all boxes. Garage receptacle partially blocked unable to test.
210.8- All garage receptacle outlets shall have GFCI protection.
210.52- A receptacle outlet shall be located with in 6' of wall at top of stair on level 2.
314.17(C)- Where boxes moved for tile NM sheath shall enter box at least 1/4" minimum.
314.25- All boxes shall have a cover. Level 3 mechanical room.
352.30- Service PVC riser shall be secured with in 36" of meter.
ELE18-02017 Final5/30/20185/31/20185/31/2018 10:12:07 AMAPASS
Grounding inspection Phone #: ###-#### Inspection requested via web by David Feller Final ok
ELE18-01755 Rough-In Permanent Service5/30/20185/31/20185/31/2018 9:42:00 AMAFAIL
Phone #: ###-#### Inspection requested via web by Bob Glenn
Make up and service not complete. Recall when ready
ELE18-01986 Temporary Service5/30/20185/31/20185/31/2018 9:05:50 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
t/s u/g n ok
ELE18-01212 Final5/30/20185/31/20185/31/2018 9:05:28 AMAPASS
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok