ELE18-02038
| Temporary Service | 5/31/2018 | 5/31/2018 | 5/31/2018 2:09:51 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE18-02039
| Temporary Service | 5/31/2018 | 5/31/2018 | 5/31/2018 1:42:04 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE18-00471
| Final | 5/31/2018 | 5/31/2018 | 5/31/2018 1:31:30 PM | P | FAIL |
|
|
It will be open. If you have any questions please feel free to contact Alan ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Dead Kitchen receps. Intersystem bond. Strap riser.
|
ELE18-00472
| Final | 5/31/2018 | 5/31/2018 | 5/31/2018 1:18:41 PM | P | FAIL |
|
|
It will be open. If you have any questions please feel free to contact Alan ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Dead Kitch, dining, Island receps. Open neutral back weather proof. Dead front Weather proof. Intersystem bond. Strap riser.
|
ELE17-01456
| Final | 5/30/2018 | 5/31/2018 | 5/31/2018 12:45:49 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Steve VanWinkle Sign only final ok
|
ELE18-02042
| Electrical Rough-In | 5/31/2018 | 5/31/2018 | 5/31/2018 12:41:21 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by jade jasper underground to future building only ok to cover
|
ELE18-01186
| Electrical Rough-In | 5/30/2018 | 5/31/2018 | 5/31/2018 11:51:03 AM | A | PASS |
|
|
Please call Kelly when you are on your way 801 710 5855 Phone #: ###-#### Inspection requested via web by Ashley White listing only ok
|
ELE17-04131
| Rough-In Permanent Service | 5/30/2018 | 5/31/2018 | 5/31/2018 11:36:16 AM | A | CANC |
|
|
We need an inspection for South end of C. Tobias is the site contact. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker
|
ELE17-04131
| Electrical Rough-In | 5/31/2018 | 5/31/2018 | 5/31/2018 11:36:00 AM | P | PASS |
|
|
We need an inspection for South end of C. Tobias is the site contact. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker ok to cover walls only
|
ELE17-03307
| Final | 5/30/2018 | 5/31/2018 | 5/31/2018 11:15:32 AM | A | PART |
|
|
Contact: Jay Gooden.... Please call 30 minutes before going so he can meet you there Phone #: ###-#### Inspection requested via web by Deb Gooden 250.104. Water piping bond shall be sized in accordance with 250.102C1. (Main water lines for both fire risers and domestic) 314.20. Boxes set back more than 1/4in shall have spark rings. (All receps in Waynes coating, Plywood and tile) 408.4 Feild identification shall be clear and evident to its specific purpose.(Circuits labeled "Recepts" shall be labeled more specificly) Disc. means shall be readily accessible. (Ice Machines)
|
ELE16-04033
| Final | 5/29/2018 | 5/31/2018 | 5/31/2018 9:09:11 AM | A | PASS |
|
|
r/i and final -- request 9am -- Chris Stans, call for onsite access Phone #: ###-#### final iok
|
ELE17-03307
| Electrical Rough-In | 5/31/2018 | 5/31/2018 | 5/31/2018 9:08:38 AM | P | PASS |
|
|
Contact: Jay Gooden.... Please call 30 minutes before going so he can meet you there Phone #: ###-#### Inspection requested via web by Deb Gooden rough in ok
|
ELE18-00870
| Electrical Rough-In | 5/30/2018 | 5/31/2018 | 5/31/2018 8:37:08 AM | A | PASS |
|
|
Equipotential Phone #: ###-#### Inspection requested via web by Kevin Koomler EQ bond only ok to cover
|