Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-03708 ELE-Aging Inspection5/31/20195/31/20196/7/2019 2:34:20 PM PASS
finaled
ELE19-00929 Electrical Rough-In5/30/20195/31/20195/31/2019 5:05:12 PMPNR
Nate Phone #: ###-#### not ready for power to be energized
ELE19-01984 Final5/30/20195/31/20195/31/2019 5:02:12 PMPFAIL
Please contact the customer before going out so they can leave work and be there when you come. Or Jamie Winters at ###-####. Phone #: ###-#### Inspection requested via web by A.M.E. Office NEC 680.23 Luminaire less than 5ft. shall be on GFCI protected branch circuit & 680.26(7) Bond gutter down spout. NEC 680.34 Required receptacle shall not be located less than 6ft. from hot tub
ELE19-01875 Final5/24/20195/31/20195/31/2019 2:04:45 PMPPASS
Phone #: ###-#### Inspection requested via web by Same Electric Final ok
ELE19-00437 Final5/30/20195/31/20195/31/2019 12:17:22 PMAPASS
Final Phone #: ###-#### Inspection requested via web by Mike McCarrel job complete, Final ok
ELE19-00438 Final5/30/20195/31/20195/31/2019 12:16:06 PMAPASS
Final Phone #: ###-#### Inspection requested via web by Mike McCarrel job complete, Final ok
ELE19-01430 Final5/30/20195/31/20195/31/2019 11:47:06 AMAPASS
door code 4657. Please call at time of inspection. Phone #: ###-#### Inspection requested via web by Ryan Wake Conference Room name changed to open office as per Joe Bruce. Final ok
ELE16-02979 Final5/29/20195/31/20195/31/2019 10:48:08 AMAFAIL
Final any questions please call Louis at ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller Receptacle near Hot Tub won`t trip when five milliamp short is applied with plug-in tester
ELE18-04765 Final5/30/20195/31/20195/31/2019 9:01:43 AMAPASS
Phone #: ###-#### Inspection requested via web by Greg Idsinga final ok
ELE19-01967 Final5/29/20195/31/20195/31/2019 8:33:29 AMAPASS
Owner said she''ll be gone for about 5 minutes around 9am but she''ll be there the rest of the morning. Owners number is ###-####. Phone #: ###-#### Inspection requested via web by sam petterson final ok
ELE19-01918 Rough-In Permanent Service5/30/20195/31/20195/31/2019 8:14:22 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough-in p/s u/g n ok