BLD05-00060
| FIRE-Final Inspection | 5/3/2005 | 5/4/2005 | 5/4/2005 3:14:13 PM | P | FAIL |
|
|
Provide building street address. Lower fire ext. in middle of back warehouse to 48" or less above floor. Provide approved door hardware on main entry/exits per. note #8 on plan review. Provide approved door hardware on office doors and rear exit door,
|
FIR04-00637
| INSP-Alarm Testing | 5/4/2005 | 5/4/2005 | 5/4/2005 2:05:05 PM | P | FAIL |
|
|
Strobe lens of fire alarm device in office is mounted too low. Code requires lens to be positioned between 80 and 96 inches.
|
FIR04-00639
| INSP-Alarm Testing | 5/4/2005 | 5/4/2005 | 5/4/2005 2:01:22 PM | P | FAIL |
|
|
Strobe lens of fire alarm device in office is mounted too low. Code requires lens position between 80 and 96 inches.
|
BLD05-00394
| FIRE-Final Inspection | 5/3/2005 | 5/4/2005 | 5/4/2005 12:16:32 PM | A | PASS |
|
|
Fire life safety finaled.
|
BLD04-02877
| FIRE-Final Inspection | 5/3/2005 | 5/4/2005 | 5/4/2005 11:48:49 AM | A | CANC |
|
|
Cancel inspection per. general contractor, not ready.
|
FIR05-00154
| INSP-Final Inspection | 5/3/2005 | 5/4/2005 | 5/4/2005 11:47:27 AM | A | CANC |
|
|
Cancel inspection per general contractor, not ready..
|
BLD04-03026
| FIRE-Final Inspection | 5/3/2005 | 5/4/2005 | 5/4/2005 11:09:28 AM | | FAIL |
|
|
It appears that portions of the fire alarm system have been installed or modified without a permit. Advised GC to stop all FA work until a FA permit and approved plans have been obtained. Need to post street address. Provide a fire ext. with current tag (none provided). Main exit must have approved hardware- see note #6 on plan review (key lock from outside only, no key availae to verify egress operation when locked). Two fire sprinkler heads are painted in the main entry stairway. Could not gain access to verify current inspection tag on sprinkler riser.
|
FIR04-00237
| INSP-Final Inspection | 5/2/2005 | 5/4/2005 | 5/4/2005 10:14:17 AM | A | FAIL |
|
|
Relocate head too far off wall 5th floor hall. Relocate head blocked in mech. room 4th floor. No sprinkler coverage required in water closets per. Bill A. Verify waterflow alarms still needed.
|
FIR04-00387
| INSP-Final Inspection | 5/3/2005 | 5/4/2005 | 5/4/2005 10:02:36 AM | A | FAIL |
|
|
Tested audible fire alarms- need signal verification. Voltage drop OK. No smoke detector at stairwell top. Wrong type detector at kitchen hallway. Need to test all smoke detectors. Need to test waterflow alarms.
|