FIR04-00258
| INSP-Sprinkler Rough-in | 5/4/2005 | 5/4/2005 | 5/4/2005 4:27:25 PM | P | PART |
|
|
Based on the plan modifications the south stairway second floor two sprinkler heads and the two at the bottom of the stairs are ok to cover
|
FIR05-00057
| INSP-Final Inspection | 5/3/2005 | 5/4/2005 | 5/4/2005 4:22:35 PM | P | FAIL |
|
|
The pendants in the soffit do not match the actual layout. Need to resubmit
|
FIR05-00219
| INSP-Sprinkler Rough-in | 5/3/2005 | 5/4/2005 | 5/4/2005 2:42:55 PM | P | PASS |
|
|
Sprinkler piping is ok to cover
|
FIR04-00768
| INSP-Alarm Testing | 5/3/2005 | 5/4/2005 | 5/4/2005 11:57:48 AM | A | PART |
|
|
The only items tested today were the battery load and the phone lines which both passed.
|
FIR05-00021
| INSP-Final Inspection | 4/28/2005 | 5/4/2005 | 5/4/2005 11:56:16 AM | A | FAIL |
|
|
Need to relocate manual pulls to more than 10' from hood. Electrical outlet at east end of hood did not turn off upon activation of hood suppression system. Also both hoods activated a single zone at the facp, so two alarms where sent but the monitoring c
|
BLD03-02531
| FIRE-Final Inspection | 5/3/2005 | 5/4/2005 | 5/4/2005 11:01:28 AM | A | PASS |
|
|
Fire life safety finaled
|
BLD03-02530
| FIRE-Final Inspection | 5/3/2005 | 5/4/2005 | 5/4/2005 11:01:03 AM | A | PASS |
|
|
Fire life safety finaled
|
BLD03-02532
| FIRE-Final Inspection | 5/3/2005 | 5/4/2005 | 5/4/2005 11:00:32 AM | A | PASS |
|
|
Fire life safety finaled
|
BLD03-02529
| FIRE-Final Inspection | 5/3/2005 | 5/4/2005 | 5/4/2005 11:00:08 AM | A | PASS |
|
|
Life safety finaled
|
BLD03-02527
| FIRE-Final Inspection | 5/3/2005 | 5/4/2005 | 5/4/2005 10:59:44 AM | A | PASS |
|
|
Fire life safety finaled
|
BLD03-02526
| FIRE-Final Inspection | 5/3/2005 | 5/4/2005 | 5/4/2005 10:59:17 AM | A | PASS |
|
|
Fire life safety finaled
|
FIR04-00547
| INSP-Supply line flush | 5/3/2005 | 5/4/2005 | 5/4/2005 10:43:23 AM | A | PASS |
|
|
Underground flush and forward flush passed
|
FIR05-00009
| INSP-Final Inspection | 5/2/2005 | 5/4/2005 | 5/4/2005 10:40:48 AM | A | FAIL |
|
|
The sidewall heads in the garage are too far off wall to meet nfpa 13 requirements
|
BLD05-00750
| FIRE-Final Inspection | 5/2/2005 | 5/4/2005 | 5/4/2005 7:30:38 AM | A | PASS |
|
|
fire life safety finaled
|
FIR05-00224
| INSP-Final Inspection | 5/2/2005 | 5/4/2005 | 5/4/2005 7:30:01 AM | A | PASS |
|
|
fire alarm finaled
|