Inspections for the day of: Thursday, May 4, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorWilliam E Thomas
TitleELE-INSPECTOR
Phone #794-9492
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00723 Final5/4/20065/4/20065/4/2006 5:16:07 PMPFAIL
###-#### - vivian
410.8 luminaire in closets
1. 2504-two closets upstairs in bedrooms
2. 2506-one closet under the stairs
ELE06-01518 Electrical Rough-In5/3/20065/4/20065/4/2006 4:40:38 PMPFAIL
ROUGH-IN FOR BONDING FOR SPA (FROM SPA TO EQUIPMENT PAD); Phone #: ###-#### Internet Inspection Request from: Barry Kendall
680.26B2 pool light needs to be bonded to forming shell
ELE06-01489 Electrical Rough-In5/4/20065/4/20065/4/2006 4:05:43 PMPPASS
I will need to meet the inspector there to provide access to the job site. Call before heading out.; Phone #: ###-#### Internet Inspection Request from: Dana Moyer
ri ok
ELE06-01546 Electrical Rough-In5/4/20065/4/20065/4/2006 3:22:36 PMPPASS
Scheduled by a contractor via Hello! on 5/4/2006 at 7:45:00 AM. Contact: ###-####.
underground conduit from service to house ok
ELE06-01488 Electrical Rough-In5/4/20065/4/20065/4/2006 2:28:46 PMPPASS
call before heading over; Phone #: ###-#### Internet Inspection Request from: Dana Moyer
ri ok
ELE06-01222 Electrical Rough-In5/3/20065/4/20065/4/2006 1:57:36 PMACANC
this is for a temproary occupancy inspection. any questions please call Aaron Alloway; Phone #: ###-#### Internet Inspection Request from: Jeff Radford
ELE06-01222 Final5/4/20065/4/20065/4/2006 1:57:10 PMPPART
this is for a temproary occupancy inspection. any questions please call Aaron Alloway; Phone #: ###-#### Internet Inspection Request from: Jeff Radford
1. t/o approved
2. lighting system does not meet the approved prints energy standards ( see attached letter at Boise City offices).
3. all aplicable cieling tiles will be removed for final inspection.
ELE06-00820 Electrical Rough-In5/4/20065/4/20065/4/2006 1:53:14 PMPPASS
###-####
walls and cielling ok to cover
ELE06-01549 Electrical Rough-In5/3/20065/4/20065/4/2006 11:37:31 AMANR
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL
conduit needs to come out of the wall that was abandoned
ELE06-00851 Electrical Rough-In5/3/20065/4/20065/4/2006 11:02:43 AMAPART
KITCHEN CEILING INSPECTION @ MONGOLIAN GRILL. THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall
cieling ok in the back areas. do not cover small hallway
ELE06-01214 Final5/3/20065/4/20065/4/2006 10:43:23 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL
no cieling inspection wasever done, need to remove the cieling tiles for inspection.
ELE06-01519 Electrical Rough-In5/3/20065/4/20065/4/2006 9:05:38 AMAPASS
concrete is poured over grounding, please contact Harvey, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters
ok to cover- dirt
ELE06-01522 Electrical Rough-In5/3/20065/4/20065/4/2006 9:05:12 AMAPASS
concrete is poured over ground, please contact Harvey, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters
ok to cover- dirt