Inspections for the day of: Friday, May 4, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01251 Rough-In Permanent Service5/4/20075/4/20075/4/2007 3:15:04 PMPPASS
gene contact ###-#### Phone #: ###-#### Internet Inspection Request from: Tracy Robertson r/i p/s u/g new ok
ELE07-01620 Temporary Service5/4/20075/4/20075/4/2007 2:21:57 PMPPASS
chris ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
t/s u/g new ok
ELE07-01619 Temporary Service5/4/20075/4/20075/4/2007 2:21:34 PMPPASS
chris ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
t/s u/g new ok
ELE07-01621 Temporary Service5/4/20075/4/20075/4/2007 2:20:58 PMPPASS
chris ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
t/s u/g new ok
ELE07-01606 Electrical Rough-In5/4/20075/4/20075/4/2007 1:43:41 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer r/i ok bath exhaust fan
ELE07-01606 Final5/4/20075/4/20075/4/2007 1:43:01 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Jarrod ok
ELE07-00393 Final5/4/20075/4/20075/4/2007 1:29:54 PMPPASS
Scheduled by a contractor via Hello! on 5/4/2007 at 7:49:07 AM. Contact: ###-####. ok
ELE07-01599 Final5/3/20075/4/20075/4/2007 12:52:52 PMPNR
This inspection if for a final. Please contact Dan Minor if there is any problems. Thank you.
Phone #: ###-#### Internet Inspection Request from: Laura Longshaw talked with contractor needs to schedule r/i for raceways covered above grid ceiling
ELE07-01588 Electrical Rough-In5/3/20075/4/20075/4/2007 11:13:56 AMAPASS
Daryl; Phone #: ###-#### Internet Inspection Request from: Andrea Whiteman
r/i ok
ELE07-01588 Permanent Service5/4/20075/4/20075/4/2007 11:12:03 AMAPASS
Daryl; Phone #: ###-#### Internet Inspection Request from: Andrea Whiteman
p/s u/g new ok
ELE07-01603 Final5/4/20075/4/20075/4/2007 10:51:10 AMANR
inspection is in bld. at very back of lot. please call have questions and may need to alter permit. thanks Phone #: ###-#### Internet Inspection Request from: joe wheeler 250.32(A) needs grd rods at shop, 225.31,32,36 needs main disconnect at shop called
ELE07-01603 Electrical Rough-In5/4/20075/4/20075/4/2007 10:48:42 AMAPASS
inspection is in bld. at very back of lot. please call have questions and may need to alter permit. thanks Phone #: ###-#### Internet Inspection Request from: joe wheeler r/i for u/g and shop ok
ELE07-01322 Electrical Rough-In5/4/20075/4/20075/4/2007 10:18:48 AMAPASS
inspect concrete over concrete encased electrode Phone #: ###-#### Internet Inspection Request from: Gary Foreman

ok for dirt cover
ELE06-04562 Rough-In Permanent Service5/3/20075/4/20075/4/2007 10:14:16 AMAFAIL
Rough-in, approval for cover on conduits and interior portion. Early morning, if possible. Phone #: ###-#### Internet Inspection Request from: Kathy Briggs
corr post for u/g 310.15 (B&C) required spacing for u/g duct bank and raceways on top of it, r/i inside fail needs secure support for emt at boxes
ELE07-01249 Rough-In Permanent Service5/3/20075/4/20075/3/2007 4:06:24 PMAPASS
Rita went in and fixed so it now shows the correct address in the system. Thanks Phone #: ###-#### Internet Inspection Request from: Tracy Robertson
r/i p/s u/g new ok
ELE07-00754 Final5/3/20075/4/20075/3/2007 3:21:01 PMAPASS
contact gene ###-#### Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok