BLD05-03494
| FIRE-Final Inspection | 5/3/2007 | 5/4/2007 | 5/10/2007 4:38:40 PM | A | PASS |
|
|
Fire life safety field inspection passed.
|
BLD05-03407
| FIRE-Final Inspection | 5/3/2007 | 5/4/2007 | 5/10/2007 4:37:44 PM | A | PASS |
|
|
Fire life safety inspection passed.
|
BLD05-02623
| FIRE-Final Inspection | 5/3/2007 | 5/4/2007 | 5/10/2007 4:36:55 PM | A | PASS |
|
|
Fire life safety finaled.
|
FIR07-00275
| INSP-Alarm Testing | 5/3/2007 | 5/4/2007 | 5/7/2007 8:47:51 AM | A | DEFR |
|
|
See inspection notes per M. Timmerman.
|
FIR07-00120
| INSP-Final Inspection | 5/3/2007 | 5/4/2007 | 5/4/2007 2:59:26 PM | A | FAIL |
|
|
Notification devices at the open office area are out of sync.
|
FIR07-00192
| INSP-Sprinkler Rough-in | 5/3/2007 | 5/4/2007 | 5/4/2007 2:58:19 PM | A | PART |
|
|
OH sprinkler rough-in is good for cover at the drop ceilings as noted on plans, two heads at one unfinished area remain to be inspected.
|
FIR06-00859
| FIR-Aging Inspection | 5/4/2007 | 5/4/2007 | 5/4/2007 1:51:15 PM | | DONE |
|
|
Building under construction, work in progress.
|
FIR07-00139
| INSP-Final Inspection | 5/4/2007 | 5/4/2007 | 5/4/2007 1:49:29 PM | A | FAIL |
|
|
See inspection comments per site visit by M. Timmerman.
|
FIR06-00780
| INSP-Final Inspection | 5/4/2007 | 5/4/2007 | 5/4/2007 1:48:03 PM | P | PASS |
|
|
Fire alarm testing completed satisfactory, permit finaled.
|
FIR07-00391
| INSP-Sprinkler Rough-in | 5/4/2007 | 5/4/2007 | 5/4/2007 1:46:56 PM | P | PART |
|
|
Core areas as indicated on work scope are acceptable.
|
FIR06-00939
| INSP-Sprinkler Rough-in/Hydro | 5/3/2007 | 5/4/2007 | 5/4/2007 1:15:36 PM | A | PART |
|
|
Noted missing coverage above the drop ceiling areas north of the kitchen, one ssu is blocked at the storage area by a roof access, missing hanger at one east branch line, approved plans not available on site as required.
|
FIR06-01002
| INSP-Sprinkler Rough-in/Hydro | 5/3/2007 | 5/4/2007 | 5/4/2007 1:12:16 PM | A | PART |
|
|
UG and OH hydrostatic tests completed, noted UG leakage within allowable limits.
|
FIR05-00270
| INSP-Sprinkler Rough-in/Hydro | 5/3/2007 | 5/4/2007 | 5/4/2007 11:44:12 AM | A | PART |
|
|
AG hydrostatic testing completed satisfactory.
|
BLD06-00591
| FIRE-Final Inspection | 5/3/2007 | 5/4/2007 | 5/4/2007 11:43:14 AM | A | FAIL |
|
|
Missing fire extinguisher, need to post max. occupant load sign, door hardware at all exterior exits is not approved, need to remove manual flush bolts, keyed locking hardware at all but the main entry/exit, and provide signage above the door, see approved plans and fire code review notes for basic requirements.
|
FIR06-00587
| INSP-Final Inspection | 5/3/2007 | 5/4/2007 | 5/4/2007 11:38:22 AM | A | FAIL |
|
|
Several areas are defficient, it does not appear work has commenced, no permit plans on site.
|
BLD06-03343
| FIRE-Final Inspection | 5/4/2007 | 5/4/2007 | 5/4/2007 9:34:00 AM | P | CANC |
|
|
justin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Inspection cancelled from web by: Victoria Beall
|