Inspections for the day of: Monday, May 4, 2009.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-00740 Electrical Rough-In5/4/20095/4/20095/5/2009 8:19:43 AMPPASS
Jay Phone #: ###-#### walls and ceilings ok
ELE08-03211 Final5/4/20095/4/20095/4/2009 4:27:25 PMPFAIL
Dave Phone #: ###-#### corr posted called 334.15 protect 10/2 at W.H., 210.8(A)(7) needs gfci all recepts within 6ft od laundry sink, 410.10 needs shower trim , correct open equip grds left and right of disposal switch wet bar area
ELE09-00747 Final5/4/20095/4/20095/4/2009 3:30:33 PMPCANC
robert Phone #: ###-#### see r/i for 05-05-09
ELE09-00151 Electrical Rough-In5/4/20095/4/20095/4/2009 3:29:57 PMPPART
mike - underground conduit Phone #: ###-#### for pole lights and sign ok
ELE09-00712 Rough-In Permanent Service5/4/20095/4/20095/4/2009 2:49:16 PMPCANC
please inspect shell. Thanks Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS see added r/i
ELE09-00712 Electrical Rough-In5/4/20095/4/20095/4/2009 2:49:00 PMPPASS
please inspect shell. Thanks Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS core shell wiring ok
ELE09-00713 Rough-In Permanent Service5/4/20095/4/20095/4/2009 2:48:16 PMPPASS
Please Inspect TI rough-in, Permanant service. Thanks Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS
r/i walls hard ceilings ok p/s u/g new ok
ELE09-00660 Final5/4/20095/4/20095/4/2009 12:17:21 PMPFAIL
Roy- call for access Phone #: ###-####
corr. met contr. 110.26(F)(2) needs required space for p/s (gas meter too close)
ESC04-01463 Site Final5/4/20095/4/20095/4/2009 10:46:27 AMAPASS
ok all work completed
ESC04-01136 Site Final5/4/20095/4/20095/4/2009 10:46:03 AMAPASS
ok lall work completed
ESC05-00063 Site Final5/4/20095/4/20095/4/2009 10:45:33 AMAPASS
ok all work completed
ESC03-01043 Site Final5/4/20095/4/20095/4/2009 10:45:08 AMAPASS
ok all work completed
ELE09-00732 Electrical Rough-In5/1/20095/4/20095/4/2009 9:34:17 AMAPASS
Ryan ###-#### r/i ok
ESC09-00135 General Inspection5/4/20095/4/20095/4/2009 9:33:35 AMAPART
r/p cleaning site
ELE09-00732 Permanent Service5/4/20095/4/20095/4/2009 9:19:37 AMAPASS
Ryan ###-#### p/s u/g new ok