FIR10-00137
| INSP-Final Inspection | 5/2/2011 | 5/3/2011 | | A | |
|
|
EARL Phone #: ###-####
|
BLD11-00043
| FIRE-Final Inspection | 5/4/2011 | 5/4/2011 | 5/4/2011 5:58:23 PM | P | PASS |
|
|
Fire life safety completed acceptable. Okayed for final - Note: Fire sprinkler permit final done although scheduled for 5/5.
|
FIR11-00127
| INSP-Final Inspection | 5/4/2011 | 5/4/2011 | 5/4/2011 5:55:04 PM | P | PASS |
|
|
Fire alarm work passed inspection. Permit finaled.
|
BLD11-00362
| FIRE-Final Inspection | 5/3/2011 | 5/4/2011 | 5/4/2011 5:54:05 PM | A | PASS |
|
|
Fire life safety inspection completed acceptable.
|
FIR10-00583
| INSP-Sprinkler Rough-in | 5/3/2011 | 5/4/2011 | 5/4/2011 5:53:01 PM | A | PART |
|
|
Inspection for cover at hard lid ceilings on the 1st and 2nd floors completed today- See plan annotations for rooms okayed for cover and rooms or areas in need of adjustment including missing coverage at combustible concealed spaces below the stairs, missing coverage at a mech. room 1st floor, blocked upright at the boys restroom 1st floor, min distance between heads at two locations is exceeded, unprotected concealed space at the 2nd floor, possible light fixture obstruction at the east entry vestibule. Rough-in at some areas incomplete at this time.
|
BLD11-00447
| FIRE-Conference | 5/3/2011 | 5/4/2011 | 5/4/2011 5:38:13 PM | A | DONE |
|
|
On site conference with owner regarding project fire life safety conditions, plan review notes, red-line comments, and items needed for occupancy approvals.
|