FIR09-00645
| INSP-Conference | 4/27/2012 | 4/27/2012 | | A | |
|
|
Contact Brian M.
|
FIR11-00569
| INSP-Conference | 5/4/2012 | 5/4/2012 | 5/4/2012 4:45:22 PM | P | DONE |
|
|
Regarding final inspection schedule and finished corrections.
|
BLD11-01032
| FIRE-Conference | 5/4/2012 | 5/4/2012 | 5/4/2012 4:41:24 PM | P | DONE |
|
|
On site discussion with contractor regarding items needed for final fire life safety approvals including fire code review note details such as premise identification, signage at the main entry/exit, PFE locations, max occupant load signs, smoke detection for HVAC units over 2000 cfm, project schedule, etc.
|
FIR12-00232
| INSP-Final Inspection | 5/3/2012 | 5/4/2012 | 5/4/2012 4:35:59 PM | P | PASS |
|
|
Hood suppression system operated correctly under test conditions. Permit finaled.
|
FIR12-00013
| INSP-Final Inspection | 5/4/2012 | 5/4/2012 | 5/4/2012 4:34:32 PM | P | PASS |
|
|
UG flush, flow switch test and final walkthrough passed. Permit finaled.
|
BLD11-00961
| FIRE-Final Inspection | 5/4/2012 | 5/4/2012 | 5/4/2012 4:32:53 PM | P | NR |
|
|
|
FIR12-00216
| INSP-Final Inspection | 5/4/2012 | 5/4/2012 | 5/4/2012 2:17:29 PM | P | FAIL |
|
|
Coverage at office room 07 is overspaced. Also need to complete hydrostatic testing per review note comments-see NFPA 25 component action replacement table. Remainder of work okayed for cover.
|
FIR12-00055
| INSP-Final Inspection | 5/4/2012 | 5/4/2012 | 5/4/2012 12:11:02 PM | P | PASS |
|
|
Field verified approved plan modifications on site. Fire alarm permit work okay for final status.
|
FIR12-00211
| INSP-Final Inspection | 5/3/2012 | 5/4/2012 | 5/4/2012 12:09:10 PM | A | PASS |
|
|
Rough-in and final inspections passed-
|
FIR12-00164
| INSP-Final Inspection | 5/4/2012 | 5/4/2012 | 5/4/2012 12:06:28 PM | P | PASS |
|
|
Inspection completed satisfactory. Permit finaled.
|
FIR12-00164
| INSP-Sprinkler Rough-in/Hydro | 5/3/2012 | 5/4/2012 | 5/4/2012 12:04:41 PM | A | PART |
|
|
Inspection intended for fire alarm test and final.
|
FIR12-00115
| INSP-Final Inspection | 5/3/2012 | 5/4/2012 | 5/4/2012 12:03:12 PM | A | PASS |
|
|
Fire alarm permit work approved for final.
|
FIR12-00100
| INSP-Final Inspection | 5/3/2012 | 5/4/2012 | 5/4/2012 12:02:18 PM | A | PASS |
|
|
Inspection passed. Fire alarm permit finaled.
|
FIR12-00155
| INSP-Final Inspection | 5/3/2012 | 5/4/2012 | 5/4/2012 11:57:43 AM | A | PASS |
|
|
Field verified noted conditions for final have been met. Fire sprinkler permit finaled.
|