Inspections for the day of: Thursday, May 4, 2017.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01055 Electrical Rough-In5/3/20175/4/20175/4/2017 12:36:32 PMPNR
Phone #: ###-#### Inspection requested via web by CHRIS CARMINE...

not ready...still digging trench
ELE17-00794 Permanent Service5/4/20175/4/20175/4/2017 12:13:03 PMPPASS
Phone #: ###-#### Inspection requested via web by William Andrews...

p/s o/h n ok
ELE17-00801 Electrical Rough-In5/3/20175/4/20175/4/2017 11:39:20 AMAPASS
meet at 11 am...

system ul listed, piping correct, grounding correct...needs to replace wiring witth THHN..will have rewiring and labels done at final
ELE17-01221 Final5/4/20175/4/20175/4/2017 10:50:28 AMPPASS
Please inspect as close to 12:00pm as possible. So we can get power turned back on with Idaho Power. If you have any questions please call Dave @ ###-#### Phone #: ###-#### Inspection requested via web by David Mackey..

job complete...ok to final
ELE17-01221 Rough-In Permanent Service5/4/20175/4/20175/4/2017 10:50:02 AMPPASS
Please inspect as close to 12:00pm as possible. So we can get power turned back on with Idaho Power. If you have any questions please call Dave @ ###-#### Phone #: ###-#### Inspection requested via web by David Mackey..

p/s o/h rec ok
ELE17-01160 Final5/4/20175/4/20175/4/2017 10:20:38 AMPPASS
Let me know if I need to change anything. Thank you. David Phone #: ###-#### Inspection requested via web by Charmel Kubik...

ok to final
ELE17-01308 Final5/4/20175/4/20175/4/2017 10:20:14 AMPPASS
Inspection requested via web by Charmel Kubik

ok to final
ELE17-01309 Final5/4/20175/4/20175/4/2017 10:19:46 AMPPASS
Phone #: ###-#### Inspection requested via web by Charmel Kubik...

ok to final
ELE17-00679 Final5/1/20175/4/20175/4/2017 9:43:22 AMAFAIL
Please call the homeowner on your way ###-#### Phone #: ###-#### Inspection requested via web by Clay Morgan...

dwn stairs bed in basement shall have ARC fault protection...210.12

panel needs labelled completely and legibly...408.4
ELE17-01269 Final5/3/20175/4/20175/4/2017 8:52:00 AMAFAIL
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON...

job not complete....open junction box, wires not terminated, no power to outlets...south junction box for outlet and light is not complete
ELE17-01268 Final5/3/20175/4/20175/4/2017 8:49:36 AMAPASS
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON...

ok to final
ELE12-02132 ELE-Aging Inspection5/4/20175/4/20175/4/2017 8:05:12 AM DONE
waiting on contractor taking over responsibility for open permit to schedule and get access
ELE12-01934 ELE-Aging Inspection5/4/20175/4/20175/4/2017 8:02:29 AM FAIL
have left messages with contractor...no attempt has been made to schedule final inspection..waiting on contractor