Inspections for the day of: Monday, May 4, 2020.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00676 Final5/1/20205/4/20205/4/2020 1:48:10 PMANR
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk
Inspected appprox 10 am, called contact about issue with smoke detectors, drove by after 1 am to check smokes which had not been repaired yet. will check back in am.
ELE20-00453 Electrical Rough-In5/4/20205/4/20205/4/2020 12:48:42 PMPPASS
under tile floor heat in master bathroom, call for access Phone #: ###-#### Inspection requested via web by steve sellers
Floor heat rough in ok cover
ELE20-01069 Electrical Rough-In5/1/20205/4/20205/4/2020 12:09:29 PMPCANC
Late afternoon please Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
ELE19-04389 Electrical Rough-In5/1/20205/4/20205/4/2020 10:17:52 AMAPASS
Please contact Trace Carson (electrician) with any questions. Go to 1710 W. Franklin the building is behind this address. Phone #: ###-#### Inspection requested via web by A.M.E. Office
ADU Wiring- 300.4(G)- an insulating bushing shall be installed on connectors containing #4 or larger conductors. 1/0 SER connectors.
ADU rough in ok cover.
ELE20-01510 Temporary Service5/1/20205/4/20205/4/2020 9:38:08 AMAFAIL
Phone #: ###-#### Inspection requested vias web by Bonnie Page
* Alternative method used- #6 copper installed, Required to be #4 minimum.
* Signage required stating altermative method used.
Contact stated would drive a ground rod t correct.
ELE20-01497 Rough-In Permanent Service5/1/20205/4/20205/4/2020 8:55:30 AMAPASS
Phone #: ###-#### Inspection requested via web by Troy Ballard
Rough in ok cover p/s u/g n ok