| INSP-Final Inspection | 4/28/2004 | 5/5/2004 | 5/5/2004 12:00:00 AM | A | FAIL |
|
|
Demo 110cd a/v as per plans. Change 30cd a/v to a 110cd a/v per plans. Repair covers on duct detectors. Provide nfpa 72 forms. 5/5/2004 10:49:15 AM
|
FIR04-00226
| INSP-Final Inspection | 4/29/2004 | 5/5/2004 | 5/5/2004 12:00:00 AM | A | PASS |
|
|
fire alarm finaled 5/5/2004 10:45:20 AM
|
BLD04-00291
| FIRE-Final Inspection | 5/4/2004 | 5/5/2004 | 5/5/2004 12:00:00 AM | A | FAIL |
|
|
Provide battery backup for the exit sign. Provide correct sticker for exit. Mount and tag fire extinguisher. Provide occupant load sign of 31 near exit. Test duct smoke detectors. 5/5/2004 9:44:39 AM
|
FIR03-00554
| INSP-Sprinkler Rough-in/Hydro | 5/4/2004 | 5/5/2004 | 5/5/2004 12:00:00 AM | A | PART |
|
|
Inspection was for covering of the piping for the first floor corridor. Piping is OK to cover but two heads need to be relocated from the supply diffusers or higher temp heads used and three pendants have not been installed yet. Head in elevator not installed yet. 5/5/2004 10:37:57 AM
|
FIR04-00261
| INSP-Final Inspection | 5/5/2004 | 5/5/2004 | 5/5/2004 12:00:00 AM | P | FAIL |
|
|
Need ceiling tile installed at sprinkler pendants. Sprinkler piping is ok to cover 5/5/2004 2:22:56 PM
|
BLD04-00044
| FIRE-Final Inspection | 5/5/2004 | 5/5/2004 | 5/5/2004 12:00:00 AM | P | FAIL |
|
|
Patch holes in rated wall in storeroom areas. Move smoke detector in open ceiling area to deck.
|
BLD04-00181
| FIRE-Final Inspection | 5/3/2004 | 5/5/2004 | 5/5/2004 12:00:00 AM | P | FAIL |
|
|
Provide exit sign/emergency light at corner of fence as shown on the approved plans 5/5/2004 2:31:47 PM
|
FIR04-00003
| INSP-Final Inspection | 5/4/2004 | 5/5/2004 | 5/5/2004 12:00:00 AM | P | CANC |
|
|
rescheduled for tomorrow morning 5/5/2004 4:05:51 PM
|