Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00624 INSP-Final Inspection4/28/20045/5/20045/5/2004 12:00:00 AMAFAIL
Demo 110cd a/v as per plans. Change 30cd a/v to a 110cd a/v per plans. Repair covers on duct detectors. Provide nfpa 72 forms. 5/5/2004 10:49:15 AM
FIR04-00226 INSP-Final Inspection4/29/20045/5/20045/5/2004 12:00:00 AMAPASS
fire alarm finaled 5/5/2004 10:45:20 AM
BLD04-00291 FIRE-Final Inspection5/4/20045/5/20045/5/2004 12:00:00 AMAFAIL
Provide battery backup for the exit sign. Provide correct sticker for exit. Mount and tag fire extinguisher. Provide occupant load sign of 31 near exit. Test duct smoke detectors. 5/5/2004 9:44:39 AM
FIR03-00554 INSP-Sprinkler Rough-in/Hydro5/4/20045/5/20045/5/2004 12:00:00 AMAPART
Inspection was for covering of the piping for the first floor corridor. Piping is OK to cover but two heads need to be relocated from the supply diffusers or higher temp heads used and three pendants have not been installed yet. Head in elevator not installed yet. 5/5/2004 10:37:57 AM
FIR04-00261 INSP-Final Inspection5/5/20045/5/20045/5/2004 12:00:00 AMPFAIL
Need ceiling tile installed at sprinkler pendants. Sprinkler piping is ok to cover 5/5/2004 2:22:56 PM
BLD04-00044 FIRE-Final Inspection5/5/20045/5/20045/5/2004 12:00:00 AMPFAIL
Patch holes in rated wall in storeroom areas. Move smoke detector in open ceiling area to deck.
BLD04-00181 FIRE-Final Inspection5/3/20045/5/20045/5/2004 12:00:00 AMPFAIL
Provide exit sign/emergency light at corner of fence as shown on the approved plans 5/5/2004 2:31:47 PM
FIR04-00003 INSP-Final Inspection5/4/20045/5/20045/5/2004 12:00:00 AMPCANC
rescheduled for tomorrow morning 5/5/2004 4:05:51 PM