Inspections for the day of: Friday, May 5, 2006.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01591 Temporary Service5/5/20065/5/20065/5/2006 3:29:52 PMPPASS
###-#### t/s o/h new ok
ELE06-00409 ELE-Aging Inspection5/5/20065/5/20065/5/2006 2:47:48 PM NR
check on job, wsuc
ELE06-01199 Permanent Service5/5/20065/5/20065/5/2006 2:28:43 PMPPASS
zane; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
p/s u/g new ok
ELE06-01200 Permanent Service5/5/20065/5/20065/5/2006 2:28:17 PMPPASS
zane; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
p/s u/g new ok
ELE06-01198 Permanent Service5/5/20065/5/20065/5/2006 2:27:55 PMPPASS
zane; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
p/s u/g new ok
ELE06-01197 Permanent Service5/5/20065/5/20065/5/2006 2:27:35 PMPPASS
zane; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
p/s u/g new ok
ELE06-01590 Electrical Rough-In5/5/20065/5/20065/5/2006 1:49:01 PMPPASS
###-#### - rick ok
ELE06-01590 Permanent Service5/5/20065/5/20065/5/2006 1:48:39 PMPPASS
###-#### - rick p/s u/g new ok
ELE05-04460 Final5/5/20065/5/20065/5/2006 1:15:17 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung 408.4 panel schedule not complete, BCC install all recepts pantry, test all wiring, open grd hall by laundry room, 110.3(A&B) access for j tub per manufactures instructions corr. called
ELE06-01525 Electrical Rough-In5/4/20065/5/20065/5/2006 11:49:40 AMAPART
darrell Note: undergr0und; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
ELE06-01121 Final5/5/20065/5/20065/5/2006 10:47:02 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ok
ELE06-01120 Final5/5/20065/5/20065/5/2006 10:46:46 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ok
ELE05-03636 ELE-Aging Inspection5/5/20065/5/20065/5/2006 9:55:02 AM FAIL
corr. called 600.5 410.15(B) 250.148 grd bell box needs hand hole and grd sign at hand hole
ELE06-01577 Temporary Service5/4/20065/5/20065/5/2006 9:28:41 AMAFAIL
ron ###-#### corr. called 310.8(D) needs sunlight resistant wire or material for mast wires, 230.23(B) needs 10ft from dirp loop to final grade
ELE06-01564 Rough-In Permanent Service5/5/20065/5/20065/5/2006 9:01:34 AMPCANC
zane; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles done in am all messed up called
ELE06-01565 Rough-In Permanent Service5/5/20065/5/20065/5/2006 9:00:02 AMPCANC
zane; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles done in am all messed up called
ELE06-01564 Electrical Rough-In5/4/20065/5/20065/5/2006 8:57:51 AMAFAIL
###-#### - corr. called shall uncover u/g covered before inspection, 310.8(D) sunlight resistant for mast wires, 300.4 nail plates, 334.30/314.17(C) staple romex within 8" of box downstairs bath 2 gang switch
ELE06-01565 Electrical Rough-In5/4/20065/5/20065/5/2006 8:55:07 AMAFAIL
###-#### - zach corr. called shall uncover u/g covered before inspection, shall use rigid for mast, 310.8(D) sunlight resistant for mast, 300.4 nail plates
ELE06-01589 Permanent Service5/5/20065/5/20065/5/2006 12:00:00 AMPCANC
###-#### - rick Note: underground voiding permit per Rick