Inspections for the day of: Friday, May 5, 2006.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00261 INSP-Final Inspection5/4/20065/5/20065/7/2006 3:25:59 PMPFAIL
The contractor has failed to request a rough-in inspection prior to ceiling cover. No inspection performed as the drop in tile must be removed to expose the installation for proper inspection. Noted shadowing at one location and missing drop ceiling at a closet with pendent sprinkler.
BLD06-00094 FIRE-Final Inspection5/5/20065/5/20065/7/2006 3:19:55 PMPFAIL
The project related fire sprinkler permit must be finaled before life safety building final approval. NOTE: the tenant has moved in prior to approval, notified the general contractor there will be no occupancy allowed prior to issuance of a certificate of occupancy.
BLD06-00667 FIRE-Sprinkler Rough-in5/5/20065/5/20065/7/2006 3:08:02 PMPCANC
No time to complete inspection, to be rescheduled per conversation with contractor.
FIR06-00296 INSP-Sprinkler Rough-in5/5/20065/5/20065/7/2006 3:06:54 PMPCANC
No time to complete inspection, to be rescheduled per conversation with contractor.
FIR05-00309 FIR-Aging Inspection5/5/20065/5/20065/5/2006 2:42:56 PM PASS
Field inspection of project related overhead fire sprinkler has been approved, permit passed inspection, is okay for final.
FIR06-00306 INSP-Final Inspection5/3/20065/5/20065/5/2006 2:27:18 PMAPASS
Fire alarm passed inspection, permit finaled.
FIR06-00280 INSP-Final Inspection5/5/20065/5/20065/5/2006 2:26:35 PMPPART
Fire alarm passed field inspection, final pending resubmittals for changed devices, modifications are clouded on the plan, EOL voltage field measured at 24.81.
FIR05-00719 INSP-Sprinkler Rough-in/Hydro5/5/20065/5/20065/5/2006 12:54:28 PMPPASS
Fire sprinkler corrections have been made, inspection passed.
FIR06-00289 INSP-Final Inspection5/5/20065/5/20065/5/2006 12:53:08 PMPPASS
Fire sprinkler work passed inspection, one missing 2nd pc. 401 canopy installed while on site.
BLD05-02218 FIRE-Final Inspection5/4/20065/5/20065/5/2006 10:48:28 AMAFAIL
The project related alarm must be approved prior to life safety final inspection approval.
FIR06-00245 INSP-Alarm Testing5/4/20065/5/20065/5/2006 10:47:28 AMAFAIL
Two HVAC units not functional to enable testing, need to provide an updated map at the panel showing new monitor points, provide as builts reflecting field changes for EOL and device addresses, provide date on NAC batteries. Two pull stations, one duct detector and a/v notification devices tested okay.
BLD06-00325 FIRE-Final Inspection5/4/20065/5/20065/5/2006 9:55:10 AMAFAIL
Need to provide suite address as indicated on review notes, need to verify path of egress lighting is installed and functional within the TI space.
FIR06-00284 INSP-Final Inspection5/4/20065/5/20065/5/2006 9:53:39 AMAPASS
Final fire sprinkler inspection passed, permit finaled.
BLD05-03448 FIRE-Conference5/4/20065/5/20065/5/2006 9:30:25 AMAPART
Some items on correction notice have been completed including door hardware, fire ext., occupant load sign, fire sprinkler. Need to provide directional arrow at the exit sign adjacent to the SW exit stairs, remove clasp for surface lock at the pantry, provide occupant load sign in the meeting room. Still need to verify emergency lighting and exit sign illumination for the path of egress, and door lock dropout upon fire alarm activation.
FIR06-00164 INSP-Final Inspection5/4/20065/5/20065/5/2006 9:24:46 AMAPART
Overhead sprinkler piping is good for cover at all areas, tape and paper at one ssu removed while on site, need to install ceiling tile and all escutcheons prior to final for this permit.
FIR05-00838 INSP-Final Inspection5/4/20065/5/20065/5/2006 9:21:57 AMAPASS
Fire sprinkler work has been completed satisfactory, permit finaled.
FIR06-00235 INSP-Final Inspection5/5/20065/5/20065/5/2006 7:43:09 AMPCANC
Please call 30 minutes prior to arrival; thanks.; Phone #: ###-#### Internet Inspection Request from: Rick Jackson Inspection cancelled from web by: Rick Jackson
FIR06-00288 INSP-Final Inspection5/4/20065/5/20065/5/2006 12:00:00 AMACANC
ROD; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles