FIR03-00082
| FIR-Aging Inspection | 5/5/2010 | 5/5/2010 | 5/11/2010 8:39:14 AM | | NR |
|
|
I spoke to jeff and ron about job status. They will let me know by friday. Follow inspection has been scheduled.
|
FIR02-00388
| FIR-Aging Inspection | 5/5/2010 | 5/5/2010 | 5/11/2010 8:24:53 AM | | PASS |
|
|
|
FIR00-00501
| FIR-Aging Inspection | 5/5/2010 | 5/5/2010 | 5/7/2010 8:50:10 AM | | NR |
|
|
I spoke to Keith Craigen again about getting this permit finaled.
|
FIR09-00551
| INSP-Final Inspection | 5/4/2010 | 5/5/2010 | 5/5/2010 3:36:47 PM | P | PASS |
|
|
Permit finaled
|
BLD04-00469
| FIRE-Conference | 5/4/2010 | 5/5/2010 | 5/5/2010 2:46:59 PM | A | DONE |
|
|
I spoke to Clint about getting this project finaled. He needs a conference for tomorrow morning to discuss the issues.
|
FIR09-00707
| INSP-Sprinkler Rough-in | 5/5/2010 | 5/5/2010 | 5/5/2010 2:45:54 PM | P | PASS |
|
|
The pendants/piping in the corridor at the pool area is ok for cover.
|
FIR09-00551
| INSP-Final Inspection | 5/5/2010 | 5/5/2010 | 5/5/2010 12:54:15 PM | P | FAIL |
|
|
Duct smoke detectors tested ok. Verification was provided for the factory installed duct smoke detectors. Need corrected map at the facp, sticker at the annunciator as discussed and nfpa 72 record of completion forms.
|
BLD08-01304
| FIRE-Final Inspection | 5/4/2010 | 5/5/2010 | 5/5/2010 10:34:12 AM | A | PASS |
|
|
Life safety passed. I discussed with Jean that the annual inspection of the fire sprinkler systems are past due. She stated that she should have this taken care of and contact me by friday.
|
BLD10-00787
| FIRE-Final Inspection | 5/4/2010 | 5/5/2010 | 5/5/2010 10:31:28 AM | A | PASS |
|
|
life safety passed
|