Inspections for the day of: Wednesday, May 5, 2010.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00082 FIR-Aging Inspection5/5/20105/5/20105/11/2010 8:39:14 AM NR
I spoke to jeff and ron about job status. They will let me know by friday. Follow inspection has been scheduled.
FIR02-00388 FIR-Aging Inspection5/5/20105/5/20105/11/2010 8:24:53 AM PASS
FIR00-00501 FIR-Aging Inspection5/5/20105/5/20105/7/2010 8:50:10 AM NR
I spoke to Keith Craigen again about getting this permit finaled.
FIR09-00551 INSP-Final Inspection5/4/20105/5/20105/5/2010 3:36:47 PMPPASS
Permit finaled
BLD04-00469 FIRE-Conference5/4/20105/5/20105/5/2010 2:46:59 PMADONE
I spoke to Clint about getting this project finaled. He needs a conference for tomorrow morning to discuss the issues.
FIR09-00707 INSP-Sprinkler Rough-in5/5/20105/5/20105/5/2010 2:45:54 PMPPASS
The pendants/piping in the corridor at the pool area is ok for cover.
FIR09-00551 INSP-Final Inspection5/5/20105/5/20105/5/2010 12:54:15 PMPFAIL
Duct smoke detectors tested ok. Verification was provided for the factory installed duct smoke detectors. Need corrected map at the facp, sticker at the annunciator as discussed and nfpa 72 record of completion forms.
BLD08-01304 FIRE-Final Inspection5/4/20105/5/20105/5/2010 10:34:12 AMAPASS
Life safety passed. I discussed with Jean that the annual inspection of the fire sprinkler systems are past due. She stated that she should have this taken care of and contact me by friday.
BLD10-00787 FIRE-Final Inspection5/4/20105/5/20105/5/2010 10:31:28 AMAPASS
life safety passed