ELE14-00283
| Final | 5/5/2014 | 5/5/2014 | 5/5/2014 3:13:03 PM | P | PASS |
|
|
Patrick Phone #: ###-#### job complete, final ok
|
ELE12-02135
| ELE-Aging Inspection | 5/5/2014 | 5/5/2014 | 5/5/2014 2:30:14 PM | | DONE |
|
|
see final
|
ELE12-02135
| Final | 5/5/2014 | 5/5/2014 | 5/5/2014 2:29:52 PM | P | PASS |
|
|
UL Listed signs, final ok
|
ELE14-01076
| Permanent Service | 5/5/2014 | 5/5/2014 | 5/5/2014 1:57:19 PM | P | PASS |
|
|
Please call Calvin when you are on your way ###-####. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan p/s u/g rec ok
|
ELE14-00902
| Electrical Rough-In | 5/5/2014 | 5/5/2014 | 5/5/2014 1:30:01 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Eddy Udry correction done, rough-in ok cover House and garage
|
ELE14-00767
| Final | 5/5/2014 | 5/5/2014 | 5/5/2014 1:00:07 PM | P | FAIL |
|
|
ceiing Phone #: ###-#### >> Inspection requested via web by Bryan McLaughlin NEC 210.8(B)(2) All kitchen 15 and 20 ampere 120 volt receptacles require GFCI protection
|
ELE14-00489
| Electrical Rough-In | 5/5/2014 | 5/5/2014 | 5/5/2014 12:54:34 PM | P | PASS |
|
|
ceiing Phone #: ###-#### >> Inspection requested via web by Bryan McLaughlin Rough-in ok cover ceiling of West store front entry.
|
ELE14-00489
| Electrical Rough-In | 5/5/2014 | 5/5/2014 | 5/5/2014 12:54:33 PM | P | FAIL |
|
|
ceiing Phone #: ###-#### >> Inspection requested via web by Bryan McLaughlin Exposed conduits traveling down column in store front entry, broken and internal diameter of the conduit has been reduced. Depth of conduit NEC 300.5
|
ELE14-00489
| Electrical Rough-In | 5/5/2014 | 5/5/2014 | 5/5/2014 12:53:17 PM | P | FAIL |
|
|
ceiing Phone #: ###-#### >> Inspection requested via web by Bryan McLaughlin Exposed PVC conduits in store front entry NEC 352.24 Internal diameter of the conduits have been reduced when relocated. NEC 300.5 Depth of conduits encased in concrete
|
ELE14-00902
| Electrical Rough-In | 5/2/2014 | 5/5/2014 | 5/5/2014 9:58:05 AM | A | FAIL |
|
|
eddy Phone #: ###-#### NEC 300.4 nail plates. NEC 334.30 stapling. missing mudrings, under stairs and in garage for concrete encased electrode
|
ELE14-00117
| Final | 5/1/2014 | 5/5/2014 | 5/5/2014 8:44:46 AM | A | PASS |
|
|
Joyce Phone #: ###-#### correction done, final ok
|
ELE14-00711
| Electrical Rough-In | 5/2/2014 | 5/5/2014 | 5/5/2014 8:21:55 AM | A | PASS |
|
|
cover track bonding and light potting Phone #: ###-#### >> Inspection requested via web by Kevin Koomler rough-in ok cover
|