Inspections for the day of: Tuesday, May 5, 2015.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00571 ELE-Aging Inspection5/5/20155/5/20155/6/2015 10:49:46 AM DONE
Drove by and inspected
ELE12-01653 ELE-Aging Inspection5/5/20155/5/20155/5/2015 4:25:52 PM DONE
Waiting for contractor to schedule
ELE15-01303 Conference5/5/20155/5/20155/5/2015 4:21:05 PMPDONE
Please call 30 minutes ahead so Brad can meet you there. Phone #: ###-#### Inspection requested via web by Kerri Hamilton Discussed underground conduits from sector box to main gear unable to reach 24" due to pilings, 300.5 note 5 permits lesser depth if encased in min of 2" of concrete.
ELE15-01217 Permanent Service5/5/20155/5/20155/5/2015 3:24:38 PMPPASS
Main gear meter # 3. p/s u/g n ok
ELE15-00702 Electrical Rough-In5/5/20155/5/20155/5/2015 2:49:05 PMPPASS
Phone #: ###-#### Inspection requested via web by kendall bender UL listing confirmed on Starbucks kiosk. Equipment ground from panel to frame work due to raceways attached. Asked contractor to label panel noting circuit for register off building emergence system. All other power from panel in kiosk. Walls of kiosk rough in ok cover
ELE15-00487 Electrical Rough-In5/5/20155/5/20155/5/2015 1:58:30 PMPPASS
Floor heat insp mst bath Call for access Phone #: ###-#### Inspection requested via web by John VanZandt Bath floor heat rough in ok cover
ELE15-01130 Permanent Service5/4/20155/5/20155/5/2015 1:33:40 PMPPASS
Phone #: ###-#### Inspection requested via web by Bryan Atkins Check GFCI protection out receptacle, overhead feed to garage, guy kit installation. p/s o/h rec ok
GCE15-00072 GCE-Final5/5/20155/5/20155/5/2015 1:03:33 PMAPASS
Greg ###-#### Final ok
GCE15-00072 GCE-Rough-In Permanent Service5/5/20155/5/20155/5/2015 1:03:20 PMPPASS
Greg ###-#### Change service for addition of HVAC. Service and AC unit rough in ok. p/s o/h rec ok
ELE15-01280 Final5/2/20155/5/20155/5/2015 12:32:11 PMPCANC
Underground for (1) light, and bonding for (4) EQ plane, (1) handrail, (1) grabrail, (1) handicap lift, (1) cage/equipment, Phone #: ###-#### Inspection requested via web by Lars Johnson Needed rough in inspection
ELE15-01280 Electrical Rough-In5/5/20155/5/20155/5/2015 12:31:38 PMPPASS
Underground for (1) light, and bonding for (4) EQ plane, (1) handrail, (1) grabrail, (1) handicap lift, (1) cage/equipment, Phone #: ###-#### Inspection requested via web by Lars Johnson Underground, bonds at 4 corners, luminaire, 3' west from S.E. corner, 2' north from S.W corner, bottom of steps for rail, top of step for bar, to equipment room in bldg. Rough in ok cover
ELE15-00754 Final5/4/20155/5/20155/5/2015 12:02:23 PMPFAIL
Inspection requested via web by Rowdy Monroe 210.52- Wall spaces 24" or wider shall have a receptacle outlet installed. Up bed.
314.25- Each box shall have covers or luminaire installed. Garage, master bath ceiling.
* No contact information provided.
ELE15-00990 Final5/4/20155/5/20155/5/2015 11:18:20 AMANH
Phone #: ###-#### Inspection requested via web by Greg Traudt No answer at door. Contractor to reschedule
ELE15-01232 Final5/4/20155/5/20155/5/2015 10:59:32 AMAPASS
final for service change, thank you Phone #: ###-#### Inspection requested via web by Rick Beckman Final ok
ELE15-01301 Electrical Rough-In5/4/20155/5/20155/5/2015 10:27:42 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Enter thru south 5 door. Storage, break room, office wall rough in ok cover
ELE15-01159 Final5/4/20155/5/20155/5/2015 9:59:37 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
ELE14-03308 Final5/4/20155/5/20155/5/2015 9:41:22 AMAPASS
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher UL listing and disconnecting means confirmed. Final ok
ELE15-01299 Permanent Service5/4/20155/5/20155/5/2015 9:33:26 AMAPASS
Request inspection for 100amp 1phase Meter Main service for Irrigation Pump.

Tim - ###-#### Phone #: ###-#### Inspection requested via web by Tim Lawrence p/s u/g n ok
ELE15-00408 Final5/4/20155/5/20155/5/2015 9:10:00 AMAFAIL
Please call cody for questions
Thanks Phone #: ###-#### Inspection requested via web by Shane Lott Starbucks track lights MC damaged at connector 110.12(B).
Unable to test all areas due to them being open and operating at time of inspection.
ELE15-01231 Temporary Service5/4/20155/5/20155/5/2015 8:40:20 AMAPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe t/s o/h n ok
ELE15-01179 Rough-In Permanent Service5/4/20155/5/20155/5/2015 8:10:08 AMAPASS
Inspection requested via web by Rowdy Monroe Rough in ok cover p/s u/g n ok