ELE13-00571
| ELE-Aging Inspection | 5/5/2015 | 5/5/2015 | 5/6/2015 10:49:46 AM | | DONE |
|
|
Drove by and inspected
|
ELE12-01653
| ELE-Aging Inspection | 5/5/2015 | 5/5/2015 | 5/5/2015 4:25:52 PM | | DONE |
|
|
Waiting for contractor to schedule
|
ELE15-01303
| Conference | 5/5/2015 | 5/5/2015 | 5/5/2015 4:21:05 PM | P | DONE |
|
|
Please call 30 minutes ahead so Brad can meet you there. Phone #: ###-#### Inspection requested via web by Kerri Hamilton Discussed underground conduits from sector box to main gear unable to reach 24" due to pilings, 300.5 note 5 permits lesser depth if encased in min of 2" of concrete.
|
ELE15-01217
| Permanent Service | 5/5/2015 | 5/5/2015 | 5/5/2015 3:24:38 PM | P | PASS |
|
|
Main gear meter # 3. p/s u/g n ok
|
ELE15-00702
| Electrical Rough-In | 5/5/2015 | 5/5/2015 | 5/5/2015 2:49:05 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender UL listing confirmed on Starbucks kiosk. Equipment ground from panel to frame work due to raceways attached. Asked contractor to label panel noting circuit for register off building emergence system. All other power from panel in kiosk. Walls of kiosk rough in ok cover
|
ELE15-00487
| Electrical Rough-In | 5/5/2015 | 5/5/2015 | 5/5/2015 1:58:30 PM | P | PASS |
|
|
Floor heat insp mst bath Call for access Phone #: ###-#### Inspection requested via web by John VanZandt Bath floor heat rough in ok cover
|
ELE15-01130
| Permanent Service | 5/4/2015 | 5/5/2015 | 5/5/2015 1:33:40 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bryan Atkins Check GFCI protection out receptacle, overhead feed to garage, guy kit installation. p/s o/h rec ok
|
GCE15-00072
| GCE-Final | 5/5/2015 | 5/5/2015 | 5/5/2015 1:03:33 PM | A | PASS |
|
|
Greg ###-#### Final ok
|
GCE15-00072
| GCE-Rough-In Permanent Service | 5/5/2015 | 5/5/2015 | 5/5/2015 1:03:20 PM | P | PASS |
|
|
Greg ###-#### Change service for addition of HVAC. Service and AC unit rough in ok. p/s o/h rec ok
|
ELE15-01280
| Final | 5/2/2015 | 5/5/2015 | 5/5/2015 12:32:11 PM | P | CANC |
|
|
Underground for (1) light, and bonding for (4) EQ plane, (1) handrail, (1) grabrail, (1) handicap lift, (1) cage/equipment, Phone #: ###-#### Inspection requested via web by Lars Johnson Needed rough in inspection
|
ELE15-01280
| Electrical Rough-In | 5/5/2015 | 5/5/2015 | 5/5/2015 12:31:38 PM | P | PASS |
|
|
Underground for (1) light, and bonding for (4) EQ plane, (1) handrail, (1) grabrail, (1) handicap lift, (1) cage/equipment, Phone #: ###-#### Inspection requested via web by Lars Johnson Underground, bonds at 4 corners, luminaire, 3' west from S.E. corner, 2' north from S.W corner, bottom of steps for rail, top of step for bar, to equipment room in bldg. Rough in ok cover
|
ELE15-00754
| Final | 5/4/2015 | 5/5/2015 | 5/5/2015 12:02:23 PM | P | FAIL |
|
|
Inspection requested via web by Rowdy Monroe 210.52- Wall spaces 24" or wider shall have a receptacle outlet installed. Up bed. 314.25- Each box shall have covers or luminaire installed. Garage, master bath ceiling. * No contact information provided.
|
ELE15-00990
| Final | 5/4/2015 | 5/5/2015 | 5/5/2015 11:18:20 AM | A | NH |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt No answer at door. Contractor to reschedule
|
ELE15-01232
| Final | 5/4/2015 | 5/5/2015 | 5/5/2015 10:59:32 AM | A | PASS |
|
|
final for service change, thank you Phone #: ###-#### Inspection requested via web by Rick Beckman Final ok
|
ELE15-01301
| Electrical Rough-In | 5/4/2015 | 5/5/2015 | 5/5/2015 10:27:42 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Enter thru south 5 door. Storage, break room, office wall rough in ok cover
|
ELE15-01159
| Final | 5/4/2015 | 5/5/2015 | 5/5/2015 9:59:37 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
|
ELE14-03308
| Final | 5/4/2015 | 5/5/2015 | 5/5/2015 9:41:22 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher UL listing and disconnecting means confirmed. Final ok
|
ELE15-01299
| Permanent Service | 5/4/2015 | 5/5/2015 | 5/5/2015 9:33:26 AM | A | PASS |
|
|
Request inspection for 100amp 1phase Meter Main service for Irrigation Pump.
Tim - ###-#### Phone #: ###-#### Inspection requested via web by Tim Lawrence p/s u/g n ok
|
ELE15-00408
| Final | 5/4/2015 | 5/5/2015 | 5/5/2015 9:10:00 AM | A | FAIL |
|
|
Please call cody for questions Thanks Phone #: ###-#### Inspection requested via web by Shane Lott Starbucks track lights MC damaged at connector 110.12(B). Unable to test all areas due to them being open and operating at time of inspection.
|
ELE15-01231
| Temporary Service | 5/4/2015 | 5/5/2015 | 5/5/2015 8:40:20 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe t/s o/h n ok
|
ELE15-01179
| Rough-In Permanent Service | 5/4/2015 | 5/5/2015 | 5/5/2015 8:10:08 AM | A | PASS |
|
|
Inspection requested via web by Rowdy Monroe Rough in ok cover p/s u/g n ok
|