FIR06-00062
| FIR-Aging Inspection | 5/5/2017 | 5/5/2017 | 5/8/2017 7:05:17 AM | | NR |
|
|
contractor is out of business
|
FIR17-00198
| INSP-Sprinkler Rough-in | 5/5/2017 | 5/5/2017 | 5/5/2017 2:06:12 PM | P | PASS |
|
|
Underground supply piping is ok to cover. A letter is being provide by the underground installer stating that the min. 4'6" cover has been provided for all of the piping
|
FIR16-00811
| INSP-Sprinkler Rough-in/Hydro | 5/4/2017 | 5/5/2017 | 5/5/2017 1:14:49 PM | P | PASS |
|
|
Underground hydro test passed
|
BLD17-00371
| FIRE-Final Inspection | 5/3/2017 | 5/5/2017 | 5/5/2017 1:14:12 PM | A | FAIL |
|
|
For final the exit signs and emergency lights needed to be installed per plans and tested. All other items appear ok. Current racks do not exceed 8'. Fire extinguishers are in place. Per Scott owner is ok to move in stock. Dale Phone #: ###-####
|
BLD16-04569
| FIRE-Final Inspection | 5/4/2017 | 5/5/2017 | 5/5/2017 11:11:46 AM | P | PASS |
|
|
life safety passed
|
BLD16-02135
| FIRE-Final Inspection | 5/4/2017 | 5/5/2017 | 5/5/2017 11:11:11 AM | P | PASS |
|
|
life safety passed
|
FIR16-00738
| INSP-Sprinkler Rough-in/Hydro | 5/4/2017 | 5/5/2017 | 5/5/2017 11:00:11 AM | A | PASS |
|
|
The remaining rough-in for the wet system basically passed with some small items that need addressed. First the plans/calculations need to be re-approved showing the additional 90's and the combustible concealed spaces at the columns and fire places need addressed. Also four dry pendants have not been installed which also needs approved.
|
FIR16-00738
| INSP-Sprinkler Rough-in/Hydro | 5/4/2017 | 5/5/2017 | 5/5/2017 10:36:13 AM | A | PASS |
|
|
200psi test of both dry systems passed
|
BLD17-00614
| FIRE-Final Inspection | 5/5/2017 | 5/5/2017 | 5/5/2017 9:43:52 AM | P | PASS |
|
|
life safety passed
|
FIR17-00122
| INSP-Final Inspection | 5/4/2017 | 5/5/2017 | 5/5/2017 9:42:59 AM | A | PASS |
|
|
permit finaled
|
FIR17-00185
| INSP-Final Inspection | 5/4/2017 | 5/5/2017 | 5/5/2017 8:09:05 AM | A | PASS |
|
|
permit finaled
|
FIR17-00184
| INSP-Final Inspection | 5/4/2017 | 5/5/2017 | 5/5/2017 8:05:37 AM | A | PASS |
|
|
permit finaled
|
BLD16-02953
| FIRE-Final Inspection | 5/4/2017 | 5/5/2017 | 5/5/2017 6:33:02 AM | A | CANC |
|
|
Duplicate inspection
|
BLD16-02951
| FIRE-Final Inspection | 5/4/2017 | 5/5/2017 | 5/5/2017 6:32:43 AM | A | CANC |
|
|
Duplicate inspection
|
BLD16-02950
| FIRE-Final Inspection | 5/4/2017 | 5/5/2017 | 5/5/2017 6:32:26 AM | A | CANC |
|
|
Duplicate inspection
|
BLD16-02949
| FIRE-Final Inspection | 5/4/2017 | 5/5/2017 | 5/5/2017 6:32:06 AM | A | CANC |
|
|
Duplicate inspection
|
BLD16-02952
| FIRE-Final Inspection | 5/4/2017 | 5/5/2017 | 5/5/2017 6:31:50 AM | A | CANC |
|
|
Duplicate inspection
|
BLD16-02948
| FIRE-Final Inspection | 5/4/2017 | 5/5/2017 | 5/5/2017 6:31:31 AM | A | CANC |
|
|
Duplicate inspection
|